Belimo UK24BAC Handbuch Technische Daten - Seite 14
Blättern Sie online oder laden Sie pdf Handbuch Technische Daten für Gateway Belimo UK24BAC herunter. Belimo UK24BAC 20 Seiten. Belimo gateway mp to bacnet ms/tp
UK24BAC
BACnet object description
Object Name
Object Type / Instance
ACT_VALUE_[n]
Analog Input
REL_FLOW_[n]
Analog Input
ABS_POS_[n]
Analog Input
ABS_FLOW_[n]
Analog Input
SNS_TYPE_[n]
Multi-state Value [n*100+3]
SENSOR_[n]
Analog Input
SWITCH_[n]
Binary Input
SUM_FAULT_[n]
Binary Value
COMMANDS_[n]
Multi-state Value [n*100+2]
14 / 20
Belimo Gateway MP to BACnet MS/TP
(continued)
Description
[n*100+0]
Actual position %
The disengaged gear is represented in the
Status-Flags (OVERRIDDEN) and in the
property Reliability.
[n*100+1]
Relative volumetric flow in % of Vnom
This value is available only for VAV
controllers and EPIV units (see
NODE_TYPE). For all other types, 65535
will be entered.
[n*100+2]
Absolute position/stroke
The unit depends on the node type:
[°] or [mm]
The disengaged gear is represented in the
Status-Flags (OVERRIDDEN) and in the
property Reliability.
If function is not supported by the actuator, a
value of 65535 will be entered.
[n*100+3]
Absolute volumetric flow (or pressure)
The unit depends on the node type:
[m3/h] for VAV controllers
[Pa] for VAV controller in STP mode
[l/min] for EPIV units
Sensor type connected to the actuator;
in the absence of sensor specification, the
wiring at the Y input of the MP actuator will
have the effect of a local override.
A conversion to °C is implemented for the
common temperature sensors (PT1000,
NI1000, NTC10K).
The setting is stored persistently.
[n*100+4]
Actual sensor value
The value is dependent on the setting in
SNS_TYPE. Alternatively, the Binary Input
SWITCH may be used for switch contacts.
[n*100+0]
Actual sensor value for switch contacts
The value is dependent on the setting in
SNS_TYPE. Alternatively, the Analog Input
SENSOR may be used for switch contacts.
[n*100+0]
Summary fault
(e.g. mechanical overload)
The fault can be reset with COMMANDS
[Reset] or with the Belimo PC-Tool.
Command
Initiation of actuator functions for
maintenance and test; the selected
command is transmitted to the actuator, after
which the Present-Value will be reset to
NONE.
T9-UK24BAC • en • v1.9 • 06.2018 • Subject to changes
Values
Default
0...100
-
0...100
-
0...65535
-
0...65535
-
NONE
NONE
ACTIVE
PASSIVE 1K
PASSIVE 20K
SWITCH
PT1000_°C
NI1000_°C
NTC10K_°C
0...65535
-
INACTIVE
-
ACTIVE
NONE
-
FAULT
NONE
NONE
ADAPTION
TEST
RESET
www.belimo.com