Belimo UK24MOD Informationen zum Produkt - Seite 3

Blättern Sie online oder laden Sie pdf Informationen zum Produkt für Gateway Belimo UK24MOD herunter. Belimo UK24MOD 20 Seiten. Mp to modbus rtu

UK24MOD
Gateway MP to Modbus RTU. MP-bus-
capable Belimo actuators can be
connected on the MP-Bus side.
 Interface MP/Modbus RTU
 Connection of MP/MPL/MFT(2)
actuators and BF-TopLine
actuators to Modbus RTU
 Up to 8 actuators and sensors can
be connected

Technical data

Electrical data
Functional data
Installation / Dimension / Weight
www.belimo.com
Belimo Gateway MP to Modbus RTU
Nominal voltage
Power supply range
For wire sizing
Connection
Supported actuators
Quantity of actuators
Communication with actuators
Maximum signal conductor lengths MP
Modbus protocol
Modbus medium
Safety
Protection class
EMC
Ambient temperature
Mounting
Dimensions
Weight
T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes
AC 24V, 50/60 Hz / DC 24V
AC / DC 21.6...26.4 V
3 VA
Modbus RTU
Plug-screw terminal, 3-pin
Supply
Plug-screw terminal, 2-pin
MP-Bus
Plug-screw terminal, 3-pin
(All terminals suitable for 2 x 1.5 mm2)
Tool
RJ12
MP/MPL/MFT(2), BF-TopLine
max. 8 pcs.
Belimo MP-Bus, Master-Slave, 1200 Bd
Dependent on the number of connected actuators,
actuator type, type of supply and signal conductor
cross-section
For details see page 5
Modbus RTU
Supported functions: 3, 6
(For register assignment, see page 11)
Medium
RTU / RS-485
Parity
NONE (1, 8, N, 2) or EVEN (1, 8, E, 1),
adjustable via DIP switch
Number of nodes
max. 32 (without repeater)
Baud rates
9'600, 19'200, 38'400, 76'800 Bd,
adjustable via DIP switch
2...100 ms, adjustable via register
Response delay
150 , adjustable via DIP switch
Termination
680 , adjustable via DIP switch
Polarisation
III Safety extra-low voltage
CE pursuant to 2004/108/EC
0...+40° C
Control cabinet installation,
can be snapped onto top hat rail 35 mm
see page 7
ca. 100 g
3 / 20