Contemporary Controls CTRLink EIDX MP Series Installationshandbuch - Seite 7

Blättern Sie online oder laden Sie pdf Installationshandbuch für Schalter Contemporary Controls CTRLink EIDX MP Series herunter. Contemporary Controls CTRLink EIDX MP Series 8 Seiten. Managed poe pse ethernet switching hubs

Port Locations
Ports 1–8 are accessed on the front panel. Other ports
are located on the bottom of the enclosure — and
for 24-port models, also on the top surface.
On all models, PoE is provided on ports 9–16
which are on the bottom of the unit.
An example of port arrangement on the top and
bottom of the enclosure is shown in Figure 6
which locates a few of the ports on the model
EIDX24MP-100T/FC.
Fault Relay
This relay is disabled by default. Its operation is
explained in the Software Manual. Its contact is
normally closed and rated at 500 mA, 24 V (max).
Console Port
The Console Port uses the standard RS-232 protocol for
configuring the switch. For proper communication :
Set the Baud rate to 9600.
Set the Data bits to 8.
Set the Parity to None.
Set the Stop bits to 1.
Set the Flow control to None.
TD071100-0IA
7
Figure 6 — Port Locations
Figure 7 — Console Port