ORBIS
Part Number ORB-MB-00002-APO
ORBIS

TIMESAvER LX

The TimeSaver Base® is a design
that provides installers with an open
working area with fixing holes shaped
to allow a fast mounting procedure.
The relay base incorporates a single-
pole voltage-free changeover contact
for switching ancillary equipment. The
maximum contact rating is 30V 1A.
When the detector changes to the
alarm state, the relay is energised,
causing the contact to change state.
14
The contact will remain in this
condition until the detector is reset.
A base is available which allows Orbis
detectors to be used in 'Sav-Wire'
detection and alarm systems. Care
should be taken to connect Sav-Wire
bases correctly as shown in fig 9.
The Orbis Heater base is designed
to be used in cold climates where
environmental conditions could
result in either icing or condensation
affecting the operation of detectors. It
TimeSaver relay base wiring connections
_
+
From
control
2
panel
COM
N/C
RELAY
CONTROLLED
DEVICE
Figure 8
Part Number ORB-RB-10004-APO
Part Number ORB-HB-00020-APO
is recommended that the heater base
be used in conjunction with either a
Waterproof Base Cover or Deckhead
Mounting Box to minimise moisture
ingress.
3
2
3
Screen
(Functional
Earth)
N/O
COM
N/C
N/O
RELAY
CONTROLLED
DEVICE
© Apollo Fire Detectors Limited 2004/JDR
ORBIS
RELAY BASE®
ORBIS
HEATER BASE
Sav-Wire base wiring connections
Remote
LED
To next
detector
Screen
(Functional
From
Earth)
+
Control
Panel
COM Not used
In +
Out + Not Used
LED - Remote indicator
NOTE: This Sav-Wire Base may be used only with compatible
control panels.
Figure 9
Part Number ORB-SW-10005-APO
ORBIS
SAv-WIRE BASE®
Part Number ORB-BA-10008-APO
ORBIS
ADAPTOR
An adaptor can be used to enable
Orbis detectors to be fitted to Series
60/65 bases.
Screen
2
3
(Functional
Earth)
1 Remote indicator +
Not used
2 + Zone connection
3 - Zone connection
4 Earth screen
© Apollo Fire Detectors Limited 2004/JDR
© Apollo Fire Detectors Limited 2004/JDR
2
3
EOL
Resistor