4EVAC Compact 500 Betriebshandbuch - Seite 11
Blättern Sie online oder laden Sie pdf Betriebshandbuch für Sicherheitsausrüstung 4EVAC Compact 500 herunter. 4EVAC Compact 500 15 Seiten. Voice evacuation system
Hacousto Holland bv
Industrieweg 87
2651BC Berkel & Rodenrijs
4EVAC Compact 500 operation manual
7. Technical specifications
Standalone system
Number of zones
Maximum total loudspeaker load
Power amplifiers
Standby power amplifiers
Loudspeaker line monitoring
Built-in
Loopdrive
Loudspeaker type
Voice messages
Storage
Message player
Controls and indications
General controls / indications
Fault indications
Zone controls / indications
Evac manual control
Fireman microphone
Power supply equipment
AC supply
AC current consumption
Inrush current
Power supply protection
Battery requirements
Type
Capacity
Charging time (80% capacity)
Rated voltage
Battery dimensions
Battery weight
Inputs
2 x BGM
6x EVAC in, 1x SILENCE in, 1x RESET in
8 x GPI
Outputs
EVAC out, FAULT out
GPO
Loudspeaker out
Amplifiers
Type
Protection
Backup amplifiers
Efficiency
Output voltage
Page 11 of 15
max. 6 local zones
600 W RMS (420W RMS pure sinewave according to EN54-16)
6 x 100 W, modular (2 channels per module), bridgeable up to 3 x 200 W
2 x 100 W / 1 x 200 W dedicated backup amplifiers
20kHz AC monitoring with EOL module, short/open/impedance deviation
loop DC monitoring with short-circuit isolators, short/open/earth leakage, EN54-
17 certified
with 100V step-down transformer
max. 16 audio files x 1 minute each, micro-SD card with content monitoring
Max. 2 simultaneous local message playback
Lamp test button, silence button, power, evac, general fault LED indicators
Power supply, system fault, network, zone fault
6 x configurable zone selection button, zone EVAC/FAULT/BUSY LED indicators
EVAC message, ALERT message, SILENCE, RESET, fireman mic with PTT button
Integrated Fireman Mic with priority and electrical monitoring
Built-in power supply system, EN 54-4 certified.
110 – 230 V AC, 50/60Hz
max. 5.3A @115V AC / 2.65A @230V AC
20A @115V AC, 40A @230V AC
Overload current limiting, over voltage shutdown, over temperature shutdown.
Sealed, rechargeable lead-acid battery for stationary use
10 – 55 Ah
< 24 h
24 V DC (2 x 12V)
2 batteries, each of max. 230 x 138 x 207 mm (LxWxH)
max. total 32.6 kg
2 x independent balanced analogue in, line-level mono, 22kΩ input impedance
monitored logic inputs, 4.7kΩ +10kΩ EOL resistors
unmonitored logic inputs (pull-down, configurable active low/hi)
Potential-free relay output (configurable NO/NC)
8 x Open collector output (configurable NO/NC)
6 x 100V transformer output, 20 kHz AC monitoring with EOL
Class D
over load shutdown, over temperature shutdown
2 dedicated backup channels, auto backup at end stage failure, auto restore
80% @ rated power
max. 100V RMS
Author:
DD