Data Aire dap4 touch Schnellstart-Handbuch - Seite 5
Blättern Sie online oder laden Sie pdf Schnellstart-Handbuch für Kontrolleinheit Data Aire dap4 touch herunter. Data Aire dap4 touch 9 Seiten. Modbus tcp/ip protocol integration
Auch für Data Aire dap4 touch: Benutzerhandbuch (8 seiten), Einbauanleitung (2 seiten), Protokoll-Handbuch (13 seiten)
FACTORY SETTINGS
TEMPERATURE: 72.0°F
DEADBAND: 2.0°F
STAGE TO STAGE: 0.3°F
ENGY SVR SETPT: 50.0°F
DEADBAND: 1.0°F
CHANGE OVER: 2.0°F
HUM SETPOINT: 50%
HUM DEADBAND: 3%
If Humidity Anticipation is turned ON in humidity setting under Factory Setting (Menu J), the following page appears
for reference (non-editable):
To change the value of any one of the setpoint values, move the cursor by pressing the ENTER key to the desired set-
point. The cursor will flash on the input value. Press the UP or DOWN button to increase or decrease the value. Once
the desired setpoint value has been changed, press the ENTER key to move to the next setting or until the cursor is at
the top of the screen.
Exit the Setpoint Menu by pressing the Esc Key. The display screen will return to the MAIN MENU. Use the UP or
DOWN Keys to advance to another Menu or press the Esc Key to return to the normal operating mode.
Note: Changes to any MENU input will remain and can only be changed manually (as described above)
Following is a brief description of the remaining menus (C through L)
The menu allows programming of night set-back, week-end or special day schedules. This is intended for use in
non-critical applications where units may be cycled off without any damage to sensitive electronic equipment. Typical
application is comfort cooling where units may be shut down during non-working hours.
Requires service level password for programming
This is a view only menu. The values are factory set and only if instructed by Data Aire engineering or service person-
nel should these be changed.
Requires service level password for viewing
Menu allows viewing of alarms, component runtime hours and re-setting of run times. Alarms will displayed by the
alarm name and the time, date of alarm occurrence. In addition, it will display the temperature and humidity at time of
alarm.
Requires service level password for programming
Humidity Anticipation
HUM SETPOINT:
TEMP OFFSET:
ANTICIPATION SP:
Menu C – Clock/Scheduler
Menu D – Input/Output
Menu E – Historical Data
(Temperature range: 65 - 85°F)
(Temperature Deadband range: 2 - 5°F)
(Stage-to-Stage range: 0.3 - 3.0°F)
(Setpoint range: 40.0 - 60.0°F)
(Deadband range: 1.0 - 5.0°F)
(Change over range: 2.0 - 5.0°F)
(Humidity range: 25-70%)
(Humidity deadband range: 1 - 15%)
50%
- 2%
48%