Data Aire dap4 touch Protokoll-Handbuch - Seite 5

Blättern Sie online oder laden Sie pdf Protokoll-Handbuch für Kontrolleinheit Data Aire dap4 touch herunter. Data Aire dap4 touch 13 Seiten. Modbus tcp/ip protocol integration
Auch für Data Aire dap4 touch: Schnellstart-Handbuch (9 seiten), Benutzerhandbuch (8 seiten), Einbauanleitung (2 seiten)

Data Aire dap4 touch Protokoll-Handbuch
11. The variable ranges can be set on the same page. Scroll to the bottom to change these ranges.
12. After you have set up your card, click Submit.
13. After your changes have been accepted, you may now change you IP address (if applicable.)
While still under the configuration tab, click network across the top of the screen.
14.
15. Under Eth0, change the IP address and Netmask to your desired values.
16. Scroll to the bottom of the screen and click submit.
17. It will take approximately 5 minutes for the IP address change to take
18. If there is no communication between the card and the BMS network, the Push Button can be
used to recall the factory setting configuration of the card: With the controller powered OFF,
turn the power ON while pressing and holding the push button. The status LED will blink red
and green rapidly for about 3 seconds, after that, it will stay as green. Wait for about 15
seconds, the LED will turn red. At this point, release the Push Button immediately. Lastly,
wait another 30 seconds for the controller to start up and establish the connection. When
started in this mode, the BMS card is reset to original factory setting temporarily; it will revert
to custom configuration (if any) after a reboot.
 
 
Data Aire's dap4 Modbus TCP/IP
Document: 600‐000‐961 version 4.0