Data Aire DAP III Anleitung Handbuch - Seite 12

Blättern Sie online oder laden Sie pdf Anleitung Handbuch für Sicherheitssystem Data Aire DAP III herunter. Data Aire DAP III 13 Seiten. Bacnet integration

Data Aire, Inc. DAP
Object Name
Blower Runtime
Condenser Runtime
Dehumidification Runtime
Energy Saver Runtime
(Optional)
Chilled Water Runtime
Analog Output 1
(Optional)
Analog Output 2
(Optional)
Fire stat Temperature Limit
High Humidity Limit
High Temperature Limit
Humidity Deadband
Low Discharge Air Temperature
Limit (optional)
Low Humidity Limit
Low Temperature Limit
Chilled Water Available Limit
(Optional)
Humidity Setpoint
Unit Start Delay
Temperature Deadband
Temperature Setpoint
Fan Speed Control
(Optional)
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
Instance
Object Description
No. AV
21
The total runtime of the blower
motor(s) (Hour)
22
The total runtime of the condenser.
This will be available when the
optional Relay module is installed
23
The total runtime of dehumidification
24
The total runtime of the energy saver
chilled water valve. This applies to
the DX unit with energy saver
cooling only.
25
The total runtime of the chilled water
valve. This point applies to chilled
water unit only
37
Optional analog output 1 Value
38
Optional analog output 2 Value
1001
Fire stat temperature limit setting
(100-150F) – Default 100 F
1002
High humidity alarm Limit setting
(10-90%). Default: 60 %
1003
High temperature alarm Limit setting
(50-90F). Default: 80 F
1004
Humidity deadband (0-15%).
Default: 3%
1005
Low Discharge Air temperature
alarm Limit setting (45-61F). This
requires an optional Discharge Air
temperature sensor. Default: 52 F
1006
Low humidity alarm limit setting
(10-90%). Default: 40%
1007
Low Return Air temperature alarm
Limit setting (50-90F). Default: 60F
1008
Chilled Water available setpoint (40-
60F). Default: 50 F. This applies to
unit that has an energy saver or
auxiliary chilled water coil.
1009
Humidity setpoint (30-70%).
Default: 50%
1010
Unit start time delay setting (5-600
seconds). Default: 5 seconds
1011
Temperature deadband (1-5F).
Default: 2F
1012
Temperature setpoint (65-85F).
Default: 72F
1013
Optional fan speed control setting
(85-100%). Default: 100%. This
option requires an Analog module.
Page 12 of 13
Present-
Value
Writeable
No
No
No
No
No
No
No
Yes-Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes- Real
value
Yes-Real
value
Yes- Real
value