Temperature & Process Measurement Indicators Setup Guide

Menu Options

Input
inPt
Allows the input type and range to be defined. There are 12 ranges
for measurement available. When a thermosensor range is selected, ie. J,
K, t, r, S, n or RTD, the instrument will automatically set the appropriate
o
C. Note: Due to the limitations of a 7-segment display, the mA
scaling in
option is displayed as na, the mV option is displayed as nu and the
ohms option is displayed as ohns.
Engineering Units
Allows the user to define the units of measurement to be displayed
unit
o
o
C,
F and Eng (linear engineering units).
in
Decimal Position
dP
Defines the position of the decimal point for the display; 0 or 1 for
thermocouples/RTD and 0 to 3 for process inputs.
High and Low Display Values
HdSP LdSP
when combined with the other scaling parameters L-iP, HdSP, and H-iP.
These 4 parameters can scale the measured input to any engineering units
as long as the relationship between the displayed units is linear. LdSP is
used to define the value to be displayed for an input defined by L-iP.
HdSP is used to define the value to be displayed for an input defined by
H-iP.
High and Low Input Values
H-iP
L-iP
which will cause the instrument to display the values set as LdSP and
HdSP. L-iP and H-iP can be input in mV, V, mA etc.
VAL
rEAd
values, either by manually entering a signal value using the VAL option or
by sampling the sensor output using the rEAd option. Values entered
manually are entered in the same way as other numeric values (see
14
The low display value LdSP is used for scaling purposes
Correspond to the signal output values from the sensor
There are 2 methods of setting the low and high input
Default: Low = 000.0, high = 100.0
20-5110 Issue G
Default: mV
Default: Eng
Default: 1