Datakom DPR-03 Installationshandbuch - Seite 2

Blättern Sie online oder laden Sie pdf Installationshandbuch für Relais Datakom DPR-03 herunter. Datakom DPR-03 2 Seiten. Voltage protection relay line to line

DIMENSIONS
INSTALLATION DIAGRAM
INPUTS AND OUTPUTS
L1-L2-L3 : Phase voltages inputs
1 : Relay output (NC)
2 : Relay output (COM)
3 : Relay output (NO)
LED INDICATORS
ON: Supply LED (green)
OUT: Relay output LED (yellow)
U<:
Under Voltage Warning LED (red)
U>:
Over Voltage Warning LED (red)
U<
U>
ON OUT MEANING
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
FLASH
ON
TECHNICAL SPECIFICATIONS
Nominal Supply Voltage: 400V-AC (L-L)
Supply Voltage Range: 260-520 V-AC (L-L)
Supply type: Capacitive, 3 phase
Frequency Range: 47-63Hz
Power Consumption: 30VA / 2W (max)
Measurement method: True RMS, line to neutral
Voltage Adjustment Accuracy: 3 %
Repetition Accuracy: 0.5 %
Over-Voltage Trip: 400-520 V-AC (L-L)
Under-Voltage Trip: 240-360V-AC (L-L)
Trip Delay Setup: 0.5 – 20 sec. adjustable
Reset Delay Setup: 0.5 – 20 sec. adjustable
Relay Output: 6A @ 277V-AC, 1800VA, 300W
Terminal wire range: max 2.5mm² (12AWG)
Screw-on Force: 0.4 Nm (3.6 lb.in)
Operating temp.: -30C (-22F) to 70 C (158F).
Storage temp.: -40C (-40F) to 80 C (176F).
Maximum humidity: 95% non-condensing.
Dimensions: 36,0x90,6x58,4mm (WxHxD)
Weight: 100 gr(approx.)
Installation: DIN Rail mounted.
Case Material: High Temp. ABS/PC (UL94-V0)
IP Protection: IP30
Conformity (EU directives)
-2006/95/EC (low voltage)
-2004/108/EC (EMC)
Norms of reference:
EN 61010 (safety requirements)
EN 60255-6
EN 61326 (EMC requirements)
Voltages OK
Under voltage warning
Under voltage trip
Over voltage warning
Over voltage trip
Phase sequence trip