Datakom DKG-171 Installations- und Betriebsanleitung - Seite 2

Blättern Sie online oder laden Sie pdf Installations- und Betriebsanleitung für Schalter Datakom DKG-171 herunter. Datakom DKG-171 2 Seiten. Transfer switch

INPUTS
DC SUPPLY: 12 or 24 volts DC, (+) and (-) terminals.
R-S-T: Mains phase voltages.
MN: Mains neutral terminal.
G: Generator phase voltage.
GN: Generator neutral terminal.
OUTPUTS
MAINS CONTACTOR: Normally closed relay output
connecting the phase-R voltage to the terminal.
(10amps@250V-AC)
GENERATOR CONTACTOR: Normally open relay
output connecting the phase-G voltage to the terminal.
(10amps@250V-AC)
REMOTE START: Normally open engine start request
relay output. Connects the battery positive voltage to
the terminal. (10amps@28V-DC)
Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: [email protected] http: www.datakom.com.tr
TYPICAL CONNECTION DIAGRAM
DATAKOM Electronics Ltd.
TECHNICAL SPECIFICATIONS
Alternator Voltage: 300 V-AC max.
Mains voltages: 300 V-AC max (Ph-N)
DC Supply Range: 8 to 33 V-DC.
Current consumption: 80mA max. (outputs open).
Wait Before Remote Start: 3 sec.
Engine Heating Period: 5 sec.
Generator Contactor Delay: 0.75 sec.
Mains Return Delay: 30 sec.
Mains Contactor Delay: 0.75 sec.
Low Voltage Limit: Adjustable from 70 to 270V-AC.
High Voltage Limit: 320 V-AC Ph-N (fixed)
Operating temp.: -20C (-4F) to 70 C (158F).
Storage temp.: -30C (-22F) to 80 C (176F).
Maximum humidity: 95% non-condensing.
Dimensions: 72x72x38mm (WxHxD)
Panel cutout dimensions: 68x68 mm
Weight: 140g (approx.)
Installation: Front panel mounted. Retaining steel
spring provided.