elsner elektronik 70165 Technische Daten und Installationsanweisungen

Blättern Sie online oder laden Sie pdf Technische Daten und Installationsanweisungen für Zubehör elsner elektronik 70165 herunter. elsner elektronik 70165 2 Seiten. Precipitation sensor

elsner elektronik 70165 Technische Daten und Installationsanweisungen
EN
KNX R sl
Precipitation Sensor
Technical specifications and installation instructions
Item number 70165
1.
Description
The Precipitation Sensor KNX R sl for the KNX building bus system detects pre-
cipitation. Two switching outputs, AND logic gates and OR logic gates are available.
The compact housing of the KNX R sl accommodates the sensors, evaluation cir-
cuits and bus-coupling electronics.
Functions:
Precipitation detection: The sensor surface is heated, so that only drops
and flakes are recognised as precipitation, but not mist or dew. When the rain
or snow stops, the sensor is soon dry again and the precipitation warning
ends
2 switching outputs (communication objects)
4 AND and 4 OR logic gates, each with 4 inputs. All switching events as
well as 16 logic inputs (in the form of communications objects) can be used
as inputs for the logic gates. The output of each gate can be configured
optionally as 1-bit or 2 x 8-bit
Configuration is made using the KNX software ETS. The product file can be dow-
nloaded from the Elsner Elektronik website on www.elsner-elektronik.de in the
"Service" menu.
1.0.1. Deliverables
Sensor
Connection cable approx. 3 m, with plug
Surface-mounted junction box (IP 55, not weatherproof)
Worm drive hose clip for pole mounting (Ø 40-60 mm)
4×50 mm stainless steel roundhead screws and 6×30 mm dowels for wall
mounting. Use fixing materials that are suitable for the base!
1.1. Technical specification
Housing
Plastic
Colour
White / Translucent
Assembly
Surface mount
Protection category
IP 44
Dimensions
approx. 62 × 55 × 155 (W × H × D, mm)
Weight
approx. 80 g
Ambient temperature
Operation -25...+85°C, storage -30...+85°C
Auxiliary supply
20...32 V DC.
An appropriate power supply unit can be pur-
chased from Elsner Elektronik.
Auxiliary current
at 24V DC: max. 90 mA
Bus current
max. 10 mA
Data output
KNX +/-
BCU type
Integrated microcontroller
PEI type
0
Group addresses
max. 254
Assignments
max. 254
Communication
54
objects
The product conforms with the provisions of EU directives.
2.
Installation and start-up
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
National legal regulations are to be followed.
Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
Do not use the device if it is damaged.
Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is
no longer guaranteed.
Precipitation Sensor KNX R sl • Version: 14.04.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Precipitation Sensor KNX R sl
The device is only to be used for its intended purpose. Any improper modification
or failure to follow the operating instructions voids any and all warranty and gua-
rantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when as-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.2. Installation location
Select an installation position on the building where the sensor can measure rain
without hindrance. No structural elements should be mounted above the weather
station, from which water could continue to drop on the precipitation sensor even
after it has stopped raining or snowing.
The mounting position must be selected so that the precipitation sensor cannot be
touched by persons.
wall
or
pole
Wall
or
pole
2.3. Position of the rain sensor
1
2.4. Sensor assembly
2.4.1. Attaching the mount
First mount the bracket for wall or pole mounting. To do this, loosen the screw con-
nection of the holder with a cross-headed screwdriver.
Wall mounting
Pole mounting
The device is mounted to the pole with the enclosed clamp.
Fig. 1
The device must be attached to a ver-
90°
tical wall (or a pole).
Fig. 2
The device must be attached to a ver-
90°
tical wall (or a pole).
Place the supply line in a loop before
leading it into the wall or junction box.
This will allow rain to drip off and not
drain into the wall or box.
Fig. 3
The device must be mounted in the
Horizontale
horizontal (transverse) direction.
1 Precipitation sensor (Area with
conductive tracks)
Hole distance 30 mm
Fig. 5 Front view
Screw the holder to the wall with two
screws. Use fixing materials (dowels,
screws) that are suitable for the base.
Make sure that the arrows point up-
wards.
Fig. 6 Botttom view
Pole
Insert the clamp through the recess in
the bracket. Tighten the clamp on the po-
le.
Make sure that the arrows point up-
wards.
1
Fig. 4