elsner elektronik Cala KNX M1-T Schnellstart-Handbuch
Blättern Sie online oder laden Sie pdf Schnellstart-Handbuch für Schalter elsner elektronik Cala KNX M1-T herunter. elsner elektronik Cala KNX M1-T 2 Seiten. Push button with temperature sensor
Auch für elsner elektronik Cala KNX M1-T: Schnellstart-Handbuch (2 seiten)
EN
Cala KNX M1-T, Cala KNX M2-T,
Cala KNX M4-T
Push Button with Temperature Sensor
Technical specifications and installation instructions
Cala KNX M1-T:
Cala KNX M2-T:
Item numbers
Item numbers
70860 (white),
70870 (white),
70872 (black)
70862 (black)
1.
Description
The Cala KNX M-T push button has touch-sensitive buttons, with which functions
in the KNX building bus system can be called, such as switch lights and devices,
dim, activate drives, send values, scenarios. A white LED is integrated into each
touch button, the behaviour of which can be adjusted.
A temperature sensor is integrated into Cala KNX M-T. An external temperature
reading can be received via the bus and processed with its own data to create a total
temperature (mixed value).
Communication objects can be connected by AND and OR logic gates.
The device is supplemented with a frame of the switch series used in the building,
and thus fits seamlessly into the interior fittings.
Cala KNX M1-T functions:
•
1 Touch bus button, can be configured as switch, selector switch, dimmer,
blind (position and slats up/stop OR down/stop), shutters (up/down/stop),
awning (in/out/stop), window (closed/open/stop), as 8 or 16-bit encoder or for
scenario recall/storage
Cala KNX M2-T functions:
•
2 Touch bus button, can be configured as switch, selector switch, dimmer,
for operating drives, as 8 or 16-bit encoder or for scenario recall/storage
•
Area function when touching both push buttons. Can be configured as
switch, selector switch, as 8 or 16 bit encoder or for scenario recall
Cala KNX M4-T functions:
•
4 Touch bus button, can be configured as switch, selector switch, dimmer,
for operating drives, as 8 or 16-bit encoder or for scenario recall/storage
•
Area function when touching two or more push buttons. Can be configured
as switch, selector switch, as 8 or 16 bit encoder or for scenario recall
Function of all models:
•
One LED per touch area. On for object value = 1 / Off for object value = 0, On
after pressing button for settable time or always off. Settable, as to whether
LED flashes at block object value = 1
•
Temperature measurements. Mixed value from own measured value and
external values (proportion can be set by percentage)
•
2 AND and 2 OR logic gates each with 4 inputs. All switching events as
well as 8 logic inputs (in the form of communications objects) can be used as
inputs for the logic gates. The output from each gate can be configured
optionally as 1-bit or 2 x 8-bit
Configuration is made using the KNX software ETS 5. The product file can be dow-
nloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the "Service" menu.
1.0.1. Area function
If the area function in ETS has been activated, another function is available alongsi-
de the regular key functions. This is triggered by touching multiple keys, e.g. if you
touch the sensor with the palm of your hand.
Using the area function
If a key is pressed and another (different) key is touched within 0.2 seconds, the ac-
tion set in the ETS is performed for the area operation (See Fig. 1 a) and b)). The keys
are then blocked for 0.5 seconds.
Using the normal key function
If a key is pressed and no other key is touched within 0.2 seconds, the normal key
function is enabled/provided for 5 seconds (See Fig. 1 c) and d)). This is extended
for 5 seconds with each push of the button.
Cala KNX M-T push button • Version: 16.09.2020 • from version 0.1.2 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Cala KNX M-T push button
Cala KNX M4-T:
Item numbers
70880 (white),
70882 (black)
Area function
Key function readiness
readiness
0s
0.2s
Area function examples
Design
Area function
Key Y
0.5 s block
a)
Key X
Design
Area function
b)
Key X
Key Y
0.5 s block
Examples of normal key functions
c)
Key X
Design
Function X
Key X
d)
Key function readiness
If the area function in the ETS is disabled, the keys can be used normally at any time.
1.1. Scope of delivery
•
Push button in casing
•
Base plate
Additionally required (not included in the deliverables):
•
Junction box Ø 60 mm, 42 mm deep
•
Frame (for insert 55 x 55 mm), compatible to the switch scheme used in the
building
1.2. Technical data
Casing
Genuine glass, plastic
Colours
• similar to RAL 9010 pure white
• similar to RAL 9005 deep black
Installation
Flush-mounted (wall installation in junction box
60 mm, 42 mm deep or cavity wall socket for
Ø
burr hole
Ø
Degree of protection
IP 20
Dimensions
Housing approx. 55 x 55 (W x H, mm),
Installation depth approx. 10 mm,
Base plate approx. 71 x 71 (W x H, mm),
Total weight
approx. 50 g
Ambient temperature
Operating -25...+80°C, storage -30...+85°C
Ambient humidity
max. 95% RH, avoid condensation
Operating voltage
KNX bus voltage
Bus current
max. 15 mA
Data output
KNX +/- Bus plug-in terminal
Group addresses
max. 183
Allocations
max. 183
Communication
Cala KNX M1-T: 44
objects
Cala KNX M2-T: 55
Cala KNX M4-T: 73
Temperature measu-
-25...+80°C
rement range
Temperature resolu-
0.1°C
tion
The product is compliant with the provisions of EU Directives.
1.2.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter Ins-
tallation position) can be corrected in the ETS in order to ensure the specified accu-
racy of the sensor (offset).
When measuring temperature, the self-heating of the device is considered by the
electronics. The heating is compensated by the software.
2.
Installation and commissioning
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
•
National legal regulations are to be followed.
•
Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
•
Do not use the device if it is damaged.
•
Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is
no longer guaranteed.
Fig. 1
5.2s
Design
Function Y
Key Y
Key function readiness
68 mm)