2. Mount the adapter plate at a suitable location on the PV racking system (typically
at the end of a row of modules).
3. Install an appropriate junction box with the adapter plate.
4. Connect the open wire end of the AC interconnect cable into the junction box using
an appropriate gland or strain relief fitting. The AC interconnect cable requires a
strain relief connector with an opening of 3/8 inches in diameter.
Step 2 - Attach AU-1P600/8002G to the Racking
1. Mark the approximate centers of each PV module on the racking system. Evaluate
the location of the micro inverter with respect to the PV module junction box or any
other obstructions.
WARNING:
ALLOW A MINIMUM OF .75 INCHES BETWEEN THE TOP OF THE ROOF AND THE
BOTTOM OF AU-1P600/8002G. WE ALSO RECOMMEND THAT YOU ALLOW .50 INCHES
BETWEEN THE BACK OF THE PV MODULE AND THE TOP OF AU-1P600/8002G. DO NOT
MOUNT AU-1P600/8002G IN A LOCATION THAT ALLOWS LONG-TERM EXPOSURE TO DIRECT
SUNLIGHT.
2. Mount one micro inverter at each of these locations using hardware recommended
by your module racking vendor
06

Step 3 - Connect the AU-1P600/8002G Wiring Harnesses

Each AU-1P600/8002G comes with one 3-pin bulkhead receptacle mounted on
the case. The three pins of this connector are for phases L1, L2 and ground. This
AC connector is oppositely sexed with the connector at the end of the extension
cable from the trunk cable through a T-connector. Plug the AC connector of the
each AU-1P600/8002G into the connector of the extension cable to form a
continuous AC branch circuit. Please check the rating label of the trunk cable for
the maximum allowable number of AU-1P600/8002G on one AC branch circuit.
WARNING:
DO NOT EXCEED THE MAXIMUM NUMBER OF AU-1P600/8002G IN AN AC
BRANCH CIRCUIT, AS DISPLAYED ON THE UNIT-RATING LABEL. For 12AWG trunk cable,
EACH AU-1P600/8002G AC BRANCH CIRCUIT MUST BE SOURCED FROM A DEDICATED
BRANCH CIRCUIT PROTECTED BY A 20A MAXIMUM BREAKER.
Install a protective end cap on the open AC connector at the end of the truck
cable.
WARNING:
MAKE SURE PROTECTIVE END CAPS HAVE BEEN INSTALLED ON ALL UNUSED
AC CONNECTORS. UNUSED AC AU-1P600/8002G WIRE HARNESS CONNECTORS ARE LIVE
WHEN THE SYSTEM IS ENERGIZED BY THE UTILITY SYSTEM.