Datexel Simply Modbus Setup-Handbuch - Seite 2

Blättern Sie online oder laden Sie pdf Setup-Handbuch für Kontrolleinheit Datexel Simply Modbus herunter. Datexel Simply Modbus 2 Seiten. Using simply modbus to read temperature with modbus slave thermocouple module

Setting the Slave ID and Read
Registers.
1. The Slave ID on the DAT3016 is 1.
2. The Register of Channel 0 is 40015.
3. As the DAT3016 is a 4 channel thermocouple
Modbus Slave we would like to read all 4 chan-
nels, so we type 4 in No. of Regs.
4. The offset is 40001.
More information on the register tables are in the
User Guide.
Sending the Command and
Receiving the Temperature.
1. Click Send.
2. If all is good the DAT3016 should return the
Temperature.
3. The result is a temperature of 254 which equals
25.4'C.
2 of 2