Cookson FDO-A10 Benutzerhandbuch - Seite 3
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Türöffnungssystem Cookson FDO-A10 herunter. Cookson FDO-A10 15 Seiten. Industrial duty fire door operator
GENERAL DESCRIPTION:
The Fire Door Operator, FDO-A10, is an integrated fire door control system. It is designed to
interface with a normally closed (NC) alarm system to control the operation of a fire door.
The control station is the standard B2 wiring.
THIS OPERATOR IS NOT A FIRE ALARM SYSTEM.
IT CAN NOT DETECT A FIRE CONDITION
1. FDO-A10 MODEL:
1.1 UNIT HAS AC POWER & NO ALARM CONDITION:
The B2 control station is used to operate the door
electrically.
Activation of the safety edge while door is closing
will cause it to reverse to full open limit.
1.2 ALARM CONDITION W/ AC POWER:
Door begins powered closure (No Delay)
If obstruction is encountered, door will reverse to open
position and attempt closure again. The door will cycle
up to 3 attempts before resting on the obstruction. If the
obstruction is removed the door will continue to the fully
closed position. (At any time the open button will raise the
door to the fully open position and begin closing immediately).
(The cycle timer will not reset).
1.3 UNIT HAS NO AC POWER:
The unit is not functional and the brake is released.
Door will close without delay.
THEORY OF OPERATION
NOTICE
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS,
USE THIS OPERATOR ONLY WITH ROLLING DOORS.
3