TESTING
1. Simulate an alarm condition and see if the solenoid disengages and releases the fire door.
2. Simulate a power failure and see if the solenoid disengages and releases the fire door.
RESETTING
1. Make sure power and alarm connection is normal.
2. Push the release latch all the way back into the slot.
3. Verify the solenoid is holding.
4. Connect fusible links to the fire door system.
Note: If the power or the alarm is not normal, solenoid will not hold. Hence the release latch will not
stay in the slot.

MAINTENANCE INSTRUCTIONS

WARNING
Check the following items at the intervals listed:
CHECK LIST DESCRIPTION
Fasteners
Check & tighten as required
Inspect door, drop-test for
Drop-test
proper operation and full closure
per NFPA-80
Inspect and service whenever a malfunction either door or release device is observed or
suspected.
Before servicing, always disconnect power supply to the release device.
Replace fuses only with those of the same type and rating.
All replacement parts must be obtained from the door manufacturer per NFPA-80.
Testing of the release device is independent of, and shall in no way be interpreted as an alternative
method of, testing of the fire alarm system, and/or any other system component employed on the fire
door or counter fire door installation. TESTING SHALL BE PERFORMED AND WITHNESSED
FOR PROPER OPERATION.
Disconnect power supply before servicing.
EVERY
EVERY
3 MONTHS
6 MONTHS
11
EVERY
12 MONTHS
Firefly IV MV