TESTING
1. Simulate an alarm condition and see if the solenoid disengages and releases the fire door.
2. Simulate a power failure and see if the solenoid disengages and releases the fire door.
RESETTING
1. Make sure power and alarm connection is normal.
2. Operate chain or crank to open the door to the fully open position.
Note: If the power or the alarm is not normal, chain or crank operation will slip and not open the door.
MAINTENANCE INSTRUCTIONS
WARNING
Check the following items at the intervals listed:
CHECK LIST DESCRIPTION
Fasteners
Drop-test
Inspect and service whenever a malfunction to either the door or release device is observed or
suspected.
Before servicing, always disconnect power supply to the release device.
Replace fuses only with those of the same type and rating.
All replacement parts must be obtained from the door manufacturer per NFPA 80.
Testing of the FCA and FKA are independent of, and shall in no way be interpreted as an alternative
method of testing the fire alarm system, and/or any other system component employed on the fire door
or counter fire door installation. TESTING SHALL BE PERFORMED AND WITHNESSED FOR
PROPER OPERATION.
Disconnect power supply before servicing.
Check & tighten as required
Inspect door, drop-test for
proper operation and full closure
per NFPA-80
EVERY
EVERY
3 MONTHS
6 MONTHS
15
EVERY
12 MONTHS
●
●
TM
M100 FireGard
Chain & Crank
02/11