Cool Expert MIC QKL mini 2 Installations- und Betriebshandbuch - Seite 9
Blättern Sie online oder laden Sie pdf Installations- und Betriebshandbuch für Temperaturregler Cool Expert MIC QKL mini 2 herunter. Cool Expert MIC QKL mini 2 13 Seiten. Cooling system intelligence

Hot gas power factor
nUP
W E
In preparation: this parameter has currently no function!
Network test
SUG
ntS
SdG
Show support group (SUG)
When pressing the lower button "<" all controllers within the same support group will signal their
group membership by winking*.
Show defrost communication group (SdG)
When pressing the lower button "<" all controllers within the same defrost communication group will
signal their group membership by winking*.
Show temperature communication group (StG)
When pressing the lower button "<" all controllers within the same temperature communication
group will signal their group membership by winking*.
Show network identification (SId)
When pressing the lower button "<" all controllers within the same network identification will signal
their group membership by winking*.
-°cool expert
-3-
MIC QKL mini 2
Display max. & min. room temperature
: 0. 5
tHI
: 7. 3
tLO
Note:
After the first start-up of the controller or after resetting the statistic values, it can last up to 15 minutes
until a value is visible.
The maximum and minimum room temperature is evaluated by sensor TL1 and is therefore only
possible in the case of the two-sensor control.
Display defrost count
dFn
Display number of door openings
dCn
Note:
Only in conjunction with configured door contact "dC" under "cI1" or "cI2"
Display number of alerts "Edo"
Edn
Display number of alerts "ECO"
ECn
Note:
The number of "ECO" alerts is recorded even if sytem monitoring is deactivated (Operating level 2
"cEE", "OFF") .
Number of power failures
PFn
Note:
In the event of power failure and restoration of power the counter under "PFN" is increased by one.
Note:
All statistical values can be reset in operating level 2 (configuration level) under the menu item "rST, rtd".
(Network support power)
1
Adjustable value 1 - 100
Show support group
(Show support group)
Show defrost communication group
(Show defrost group)
Show temperature communication group
StG
(Show temperature group)
Show network identification
SId
(Show network identifikation)
Network service message
nSP
(Network servicepin)
Maximum room temperature "tL1"
(Temperature High)
Minimum room temperature "tL1"
(Temperature Low)
(Defrost Number)
1
The number of defrosting processes
(Door Contact Number)
18
Number of door openings
2
Number of "Edo" alerts
3
Number of "ECO" alerts
2
Number of power failures
Network service message (nSP)
When pressing the lower button "<" a network service message is send.
Note:
"-A-" is shown if a message is sent successfully. The blinking Alarm-LED indicates an error when
trying to send a message (e.g. no network module present, communication deactivated).
*winking: a winking controller shows a rotating "°
Back to the configuration level (operating level 2)
(Network test)
-2-
Version number
Idn
Diagnostic values (Cool Expert internal)
d_1
d_6
Note:
The values above are needed for diagnosis in the case of service by Cool Expert and are
insignificant for the normal operation.
Back to operating level (operating level 1)
-1-
(ECO Number)
(ECO Number)
(Pfn Number)
" in the display for aprox. 5 seconds and can
The first menu item after changing to the
cS
configuration level (operating level 2)
The statistics level
"i_0": no network interface registered
i_0
"i_1": network interface registered
i3. 0
Displays Network interface version
. 3 8
Displays software version
. 1
Displays software subversion
r19
Displays control version
cE3
Displays device name
d_2
d_3
d_4
d_7
d_8
d_9
The first menu item after changing to the
tL1
operating level (operating level 1)
Operating level 3
(Ident Number)
d_5
9