No. 15: BUS TERMINATION
Caution: Switch off the system before Setting the Jumper.
Read the MODBUS/CANBUS instruction manual to learn about the operational functions available.
Jumper Setting always active during alla states of the system.
Functional Setting
Bus termination
No. 5: CHARGING LEVEL Current:
No. 11: Auxiliary Output "AUX 1"
RJ 11 behind the label, remove the window label to find the connector.
It is possible connect:
Temperature sensor, for ambient temperature charging
compensation. With this it is possible to active the
specifications of the EN54-4 firing norm.
Compensation Recharges in temperature
Connecting to RJ11 AUX1 Auxiliary Output the cable RJTEMP11 (supplied separately), the CBI will vary the voltage of
battery charging depending on the temperature:
Fast Charge
+/-5mV/°C x n. of Cells from -8°C to +60°C
+140mV/Cell ÷ -200mV/Cell compared to the value
at 20°C
If the temperature is less than -20°C or greater than +60°C alarm is signalled with code 7 blink.
The sensor place on cable RJTEMP11 must be applied on the battery.
If the sensor is not connected or if the sensor is defective, the led Low Batt is on and the led Diagnosis continues to
show the status of the battery: trickle charge, fast charge or recovery charge.
No. 13: TIME BUFFERING Setting
Time buffering it is enabled when the Input main is switched OFF. It is possible setting by the position of the rotate
switch TIME BUFFERING.
The output LOAD time ON depending on position of the Switch.
Switch positions:
Switch position
Time Buffering (min.)
If the switch is in 0 position the Time Buffering maintain ON state until the battery it is completed discharged. Anyway
to prevent risk of damage, the product disconnect the batteries when a minimum voltage level is reached.
No. 14: Auxiliary Output "AUX 2"
Connection MODBUS/CANBUS via RJ45 connector. See instruction for MODBUS communication protocol. (CANBUS
to be implemented)
No. 15: Auxiliary Output "AUX 3"
Connection MODBUS/CANBUS via RJ45 connector. See instruction for MODBUS communication protocol. (CANBUS
to be implemented)
Battery Care
The Battery Care philosophy is base on algorithms that implement rapid and automatic charging, battery charge
optimization during time, flat batteries recovery and real time diagnostic during installation and operation. The Real
Time Auto-diagnostic system, monitoring battery faults such as, elements in short circuit, accidental reverse polarity
connection, disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis
Led; during the installation and after sell. Each device is suited for all battery types, by means of jumpers it is possible
setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel and Ni-Cd. They guarantees battery reliability in
It is possible set the max recharging current for the batteries by trimmer (Battery Charging
Level). The current adjustment goes from 20% ÷ 100% of In. Set the maximum charging
current between 10% and 20% of the battery capacity.
0
1
2
0.5
2
Trickle charge
+/-3mV/°C x n. of Cells from -20°C to +60°C
+120mV/Cell ÷ -120mV/Cell compared to the value
at 20°C
3
4
5
5
10
15
6
7
8
20
30
45
9
60