During the initial filling of the main pipeline, there may not be enough back-
pressure downstream from the filter to allow the cleaning cycle to function
properly. Therefore, it is necessary to install a valve at the outlet to be partially
closed (i.e., gate valve, ball valve or butterfly valve). Once the total system is fully
charged, the downstream valve can be adjusted as desired.
☐ Do not proceed until the tasks above have been completed
Initiate the first cleaning cycle as described in "Section 1.3". During the first
cleaning cycle, air in the system will be expelled, so it may require more than one
cycle to achieve proper cleaning.
☐ Do not proceed until the tasks above have been completed
Confirm that the differential pressure indicator is not showing a pressure
difference at this point. When the filter is clean, the pressure difference should
not exceed 0.1 bar.
☐ Do not proceed until the tasks above have been completed