AirCycler g2-k Schulungshandbuch - Seite 14

Blättern Sie online oder laden Sie pdf Schulungshandbuch für Thermostat AirCycler g2-k herunter. AirCycler g2-k 20 Seiten.
Auch für AirCycler g2-k: Installations- und Benutzerhandbuch (11 seiten), Handbuch für Installationsprüfungen (2 seiten), Handbuch für Installationsprüfungen (2 seiten)

AirCycler g2-k Schulungshandbuch

5.0 CALCULATED TIME SETUP

5.1 SETTING NUMBER OF MINUTES PER HOUR OF SUPPLIED AIR FLOW REQUIRED
Enter the minutes per hour that you require fresh air to be brought into the home. Factory
default is 20 minutes. Press MODE to advance to the next setting.
For installations without the FanConnect™ switch, continue to section 5.4.

5.2 SETTING MINUTES OF EXHAUST FAN RUN TIME REQUIRED

Enter the desired minutes/hour for exhaust fan run time. Factory default is 20 minutes.
If the FanConnect™ switch is not detected, make sure it is in the OFF position. Press MODE.

5.3 SETTING OPTIONAL MIXING TIME

If the user needs more central fan time for whole house mixing than the amount that is
provided by ventilation time, the central fan can be configured to run an additional time
period to complete the mixing period. Factory default is 0 or OFF. The fresh air damper
will not be open during this extra time. Press MODE to advance to the next setting.

5.4 SETTING OPERATION HOURS

If the user does not want the ventilation system to run constantly, you can set ON time
and OFF time. Factory default is off.
If you are not setting an ON and OFF time, press MODE and continue to section 5.6.
If you select YES, the AirCycler® g2 will prompt you to enter the hour you would like the
ventilation to begin and the hour you want it to end followed by the current time.
N
Set the hour for ventilation to START. Press MODE to advance to the next setting.
Set the hour for ventilation to STOP. Press MODE to advance to the next setting.

5.5 SETTING CURRENT TIME

Enter the current time. Press MODE to advance to the next setting.
If you are not connecting a FanConnect™ switch, Press MODE until Normal Operation is
resumed. CALCULATED TIME SETUP IS COMPLETE

5.6 SETTING EXHAUST FAN DELAY TIME

Set the desired length of time you would like the bath fan to run after the FanConnect™
has been turned off. Factory default is 10 minutes.
Press the DOWN arrow until the countdown reaches 0 then SL (SL= slave mode). In slave
mode the exhaust fan runs anytime the central fan is running with the fresh air damper
open. Slave mode will provide a "balanced" mode of operation.
Press MODE to save all settings and return to normal operation.
CALCULATED TIME SETUP IS COMPLETE.
The AirCycler® g2 will now return to normal operation.
14
AC DOC 8.5
REV 7/2020