AUTOMATION 2000 DGPT2 Series Technische Anweisungen - Seite 11
Blättern Sie online oder laden Sie pdf Technische Anweisungen für Transformator AUTOMATION 2000 DGPT2 Series herunter. AUTOMATION 2000 DGPT2 Series 17 Seiten.
6.6 Thermometer
- 1 fluid expansion thermometer with tracking pointer access that can be sealed
by lead
Indicator diameter: 50 mm
- Ambient temperature compensation
- Tracking pointer indicating maximum temperature reached
- Display scale: 40–150°C
- Reading accuracy: ±1°C
- Measure accuracy: ±4°C at 60°C, ±1.5°C at 90°C
6.7 Fitting
- Fitting at the base of the housing through a flange in composite with a thermowell
to be installed on a 60 mm diameter opening (FPM seal and fixing hooks supplied).
Flange diameter: 85 mm
Thermowell: 104 mm (length), 27-24 mm (diameter from top to bottom end)
- The flange and the thermowell do not conduct electricity.
6.8 Operating conditions
- Ambient temperature: –40°C to 65°C
- Dielectric temperature: ≤ 140°C
6.9 Breaking capacity
Function
Gas discharge
Excessive pressure
Temperature
6.10 Standard compliance
The DGPT2
conforms to the following Standards:
®
IEC EN 50216-1
IEC EN 50216-3
IEC EN 60529
NF EN 60439-1
NF EN 60950
NF C17-300
NF C52-107
TECH. INSTRUCTIONS
DGPT2
®
A U T O M A T I O N 2 0 0 0
RESISTIVE LOAD - L/R < 40 ms
24 VDC
48 VDC
1 A
1 A
2 A
3 A
4 A
4 A
110 VDC
220 VDC
0.5 A
0.5 A
1 A
Page
N° T/NOT-0021
11
250 VAC
50/60 Hz
Cos φ 0.5
0.25 A
1 A
0.25 A
5 A
0.5 A
8 A
Date: 28/09/16
Rev.
7