HID VertX EVO V1000 Installationshandbuch - Seite 7

Blättern Sie online oder laden Sie pdf Installationshandbuch für Controller HID VertX EVO V1000 herunter. HID VertX EVO V1000 19 Seiten.

HID VertX EVO V1000 Installationshandbuch
VertX EVO V1000 Installation Guide
CAUTION: The V1000 RS-485 Ports 1 & 2 (P3) are a common bus and therefore cannot have panels with
duplicate Interface Addresses assigned. The same is true of the V1000 RS-485, Ports 3 & 4 (P4). For
example, two panels, both with Interface Address 0 (factory default), cannot be connected to Ports 1
and/or 2 (P3).
Wire the RS-485 to the In position only of the P9 terminal block for the V100-Series panel. This is especially
important when the RS-485 communication is in a "daisy chain" configuration. If the RS-485 is wired In and Out,
and power is lost, or the P9 terminal block is unplugged on a V100-Series panel, RS-485 communications will be
lost to downstream V100-Series panels.
4.
Output Connections (VertX EVO V1000) –
All Output connections are used for general purpose controls. The following
table shows where the various outputs are located. Pin numbers shown use the
convention "NO/C/NC". For example, Output 1, V1000: P14 Pin 3 is NO
(Normally Open,) Pin 4 is C (Common,) and
Pin 5 is NC (Normally Closed).
Note: Relays are dry contact rated for 2Amps @ 30VDC.
Output
number
1
2
CAUTION: Some magnetic locks exhibit both high inrush current when activated and a high
instantaneous break voltage when de-energized due to magnetic field collapse. Use a snubber circuit
across the controlling relay terminals to protect the controlling relay contacts. Go to
support.hidglobal.com, see Solution 891 - How do I wire a High In-Rush Current locking device to
VertX/Edge/Edge Solo?.
July 2011
V1000
P14 Pins 3/4/5
P11 Pins 3/4/5
© 2003 - 2011 HID Global Corporation. All rights reserved.
Page 7 of 19