AirCycler FRV Installations- und Benutzerhandbuch - Seite 3
Blättern Sie online oder laden Sie pdf Installations- und Benutzerhandbuch für Zeitschaltuhr AirCycler FRV herunter. AirCycler FRV 7 Seiten. Digital programmable furnace fan timer
INSTALLATION CONSIDERATIONS
The AirCycler® model does not require batteries. It does require 24 VAC (R and C terminals) to be connected for
proper operation. The AirCycler will not operate without these two connections.
The wires (R, C, W & Y ) from the air handler to the thermostat can run parallel with the wiring from the AirCycler®
to the air handler. The fan wire (G) needs to be interrupted by the AirCycler®. Some thermostats do not require a
(C) connection. The AirCycler® requires a (C) for power, which must be wired to the furnace.
Air Handler
w
w
w
WIRING DIAGRAM
AirCycler
.
a
i
r
c
y
Y - Cooling
R - 24 VAC Power
W - Heating
Gt - Fan to Thermostat
FRV
®
c
l
e
r
.
c
KEY
Gf - Fan to Furnace
C - Common
V - Vent
Thermostat
Blue
Damper
Red
White
o
m
3