DynaLock 3101B-TJ101 Verdrahtungshinweise - Seite 3
Blättern Sie online oder laden Sie pdf Verdrahtungshinweise für Schlösser DynaLock 3101B-TJ101 herunter. DynaLock 3101B-TJ101 13 Seiten. Electromagnetic lock
Auch für DynaLock 3101B-TJ101: Montageanleitung (4 seiten)
MODEL 3101B-TJ101
DELAY EGRESS SYSTEM
705 Emmett Street Bristol, CT 06010
WIRING INSTRUCTIONS
1-877-DynaLock www.dynalock.com
BASIC WIRING
Basic hook-up is shown below. For other system features hook-up see "Option Wiring" (page 7).
POWER
Terminals 1& 2 - Power Input. May be 12 or 24 Volts, AC or DC,
FAC
uninterrupted. Current requirement is 0.75 Amps for 12 Volts and 0.5 Amps
1 2
3 4
for 24 Volts (check voltage selection jumpers "V" - page 1).
DO NOT INTERRUPT INPUT POWER (TERMINALS 1 & 2) FOR
AUTHORIZED ACCESS/EGRESS. EXTERNAL ACCESS/EGRESS
CONTROLS (EX. KEYPAD, CARD READER, ETC.) SHOULD USE
DEDICATED BYPASS TERMINALS 7 & 8 or 9 & 10 (SEE PAGE 11).
Terminals 3 & 4 - Fire Panel Input. May be normally-open (N.O.) or
normally-closed (N.C.) dry contacts from fire panel (check fire alarm control
jumper "FA" - page 1).
When the fire panel trips, the 3101B-TJ101 will release, the audible will
sound a constant tone and the bi-color LED (LED1) will change to green.
When the fire panel is reset, the 3101B-TJ101 will reset and lock.
NOTE: DO NOT APPLY POWER TO TERMINALS 3 & 4 OR DAMAGE
WILL OCCUR.
PROPER OPERATION OF THE 3101B-TJ101
REQUIRES
ADJUSTMENT OF THE EGRESS SENSOR
PROCEED TO EGRESS SENSOR ADJUSTMENT
Page 3
3101B-TJ101 MANUAL
03/11