AutomationDirect Productivity2000 P2-04AD-1 Handbuch - Seite 3

Blättern Sie online oder laden Sie pdf Handbuch für E/A-Systeme AutomationDirect Productivity2000 P2-04AD-1 herunter. AutomationDirect Productivity2000 P2-04AD-1 8 Seiten. Analog input

Wiring Diagram
Current Input Circuits
An Edison S500-32-R 0.032A fast-acting
fuse is recommended for current loops.
2-Wire 4-20 mA
Transmitter
+
2-Wire Transmitter
+
+
3-Wire Current
Transmitter
3-Wire Transmitter
+
4-Wire 4-20 mA
Transmitter
User Supplied
AC or DC
Transmitter Power
4-Wire Transmitter
Note: Do not connect both ends of shield.
Sales 800-633-0405
fuse
I+
.032A
+
+24VDC User
Supplied Power
COM
fuse
I+
.032A
+
+24VDC User
Supplied Power
COM
fuse
I+
.032A
COM
Schematic
MODULE CIRCUITRY
COM
I1+
I2+
I3+
I4+
COM
COM
COM
COM
COM
COM
COM
0V
-
+
24V+
24 VDC User
Supplied Power
www.productivity2000.com
INTERNAL
CH1 ADC
CH2 ADC
CH3 ADC
CH4 ADC
ISOLATED ANALOG
CIRCUIT POWER
ISOLATED ANALOG
CIRCUIT COMMON
3