3. Units maybe
mounted directly to the ceiling using the plastic screw anchors packed with the bracket. For direct mount-
ing, the bracket is used as a template and 3/16-inch holes are drilled for the screw anchors.
TAMPER RESISTANCE
This detector includes a tamper-resistant
feature that prevents its remova[ from the base without the use of a tool.
TO
enable this feature, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab before installing
the detector. The tamper resistant tab is on the detector mounting base.
To remove a tamper-resistant
detector from the base, use a pocket screwdriver,
or aimi[ar tool, to depress the tamper-
resistant tab and turn the detector counterclockwise.
The tab is accessible through the slot on the mounting baee.
WIRING INSTALLATION
GUIDELINES
All wiring must be installed in compliance
with local electrical codes and the requirements
of the authority having jurisdic-
tion.
The conductors
used to connect the smoke detectors to the control panel should be color to reduce the [ikelihood of
wiring errors. Improper connections
can prevent a system from responding
properly in the event of a fire.
For signal wiring (the wiring between interconnected
detectors),
it is recommended
that the wire be no smaller than 18
gauge (1.0 mm ) in cross sectional
area. However, the screws and clamping
plate in the base can accommodate
wire
sizes up to 12 gauge (2.5 square mm). The use of twisted pair wiring or shielded cable for the power (+ and -) loop is
recommended
to minimize the effects of electrical interference.
if shieided catie is used, the shield connection
to and from. the aeteclar mus; & ~ntinucw
by using wire nuts, ctimping,
OPTIOWL
cmL5 SHIELD
A78.?s%o,
Figure 3. Typical Wiring Diagram for a 2-Wire Loop.
or soldering, as appropriate,
for a reliable connection.
Make connections
by stripping about 3/8" (1 O mm) of insulation from the end of the wire. Then, slide the wire under the
clamping plate and tighten the clamping plate screw. Do NOT loop wires around the terminal.
Check the zone wiring of all bases in the system before installing detectors in them. This includes checking the wiring for
continui~,
correct polarity, and performing
a dielectric test,
DETECTOR
ID NO.
The detector is addressed
via a unique internal serial number sequentially
stored in the detector's special circuits. Refer
to the suppofling
Ademco control panel installation
instructions for the appropriate
information.
TESTING THE 4192CPM
SENSITIVi~
Note: Before testing, notify the proper authorities
that the smoke detector system is undergoing
maintenance
and, there-
fore, will be temporarily
out of service. Disable the system undergoing
maintenance
to prevent unwanted alarms.
Note: Before testing the detector, check for the presence of the bhnking LED. If it does not blink, power has been lost to
the detector (check the wiring) or it is defective (return for repair).
Detectors must be tested after installation
and periodic maintenance.
Test the sensitivity of the 4192CPM in the following
two
ways:
A. Test Switch
1. Press and hold the test switch for 10 seconds.
2. An alarm should be annunciated
at the system's control or console within 10 seconds, Some systems also cause the
detector's LED to latch on during the alarm. Otherwise, the LED continues to blink eve~ 10 seconds.