5192CP Addressable ionization Smoke Detector
Installation and Maintenance Instructions
Before instalhng detectors, please thoroughly read the suppoding Ademco control panel installation instructions, which prc,vide de-
tailed information on detector spacing, placement, zones, and special applications, copies of the i"stal[atio" instructions ~Lre~vai[.
able from Ademco. NFPA 72 and NEMA guidelines should also ba obsewed.
GENERAL DESCRIPTION
The Model 5192CP ionization smoke detector uses a state-o f-the-ati sensing c:hamber. This detector is designed to provide
open area protection and to be used with compatible UL-listed Ademco control panels, An LED on each detector flashes eve~
four seconds, This LED can be latched on by code command from ceflain control panels to indicate an alarm. It can also be
unlatched to the normal blinking condition by the same control parlels. The 519:?CP detector is intended for use in an Ademco
2-wire polling loop system. It is addressed by either dip switch or internal seritxl number and has high and low maintenance
signals that may be disabled with dip switch position 8. A three-screw, removable terminal block is used to connect to the sys-
tem. 8oth detector power and communication between detector and control paoal are accompkshed
over the same tti,o wires.
SPECIFICATIONS
Diameter ~ncluding mounting bracket):
5.5 inches (140 mm)
Height (including mounting bracket):
1.7 inches (43 mm)
Weight
5.3 ounces (150 grams)
Operating Temperature Range
32" to 120"F (W to 49°C)
Operating Humidi~ Range
10O/.to 930/o relative humidity, noncondensing
StaR-up Tme
30 seconds maximum
System Voltage
12 v
Standby Current (m=imum
@ 12v):
LED off
1.3mA
LED on:
3.1 mA
MOUNTING
INSTRUCTIONS
Each 5192CP detector is supp~ed with a mounting bracket that pemits the detector to be mounted:
1. To a single gang box.
2. Directly to a 31/>inch or 4 inch octagonal box.
3. To a 4 inch square electrical box by using a plaster ring.
TAMPER RESISTANCE
This detector includes a tamDer-resistant feature that vrevents its removal from the Ibase without the use of a tool. To enable this fea.
ture, remove the smaller tab'by breaking it at the sctibed fine on the tamper resistard tab on the detector mounting bracket (see Fig-
ure 2), then install the detector. To remove a detector from the bre,cket once it has been made tamper resistant, use a small
screwdriver to depress the tamper-resistant tab located in the slot on !he mounting bracket, and turn the detector c~untercl<>ctise.
A78-2653-W
figure 1. Sutiace Mounting on 3112 inch and 4 inch octagon box
A7B-2333-02
Figure 2. Detector mounting bracket
AD400-19-00
1
156-1001-03
Ademco, 165 Eileen Way, Syosset, NY 11791