ActivePure Induct Guardian I Handbuch - Seite 11
Blättern Sie online oder laden Sie pdf Handbuch für Luftreiniger ActivePure Induct Guardian I herunter. ActivePure Induct Guardian I 16 Seiten.
TROUBLESHOOTING GUIDE
This unit must be installed and serviced by a licensed HVAC contractor or
electrician. Failure to do so will void the warrant of the product.
Caution
• UV Light in operation; disconnect unit from power cord before servicing; failure
to follow warnings may result in severe eye damage
• Live voltage may be present
WARNING
TROUBLESHOOTING GUIDE FOR ACTIVEPURE
Tools Required:
• 1/4 Nut Driver
• Phillips Head Screwdriver
• Multimeter
• Small Flat Head Screwdriver
• Flashlight
1. Check the incoming voltage by unplugging the power cord from the side of the ActivePure
Guardian I and placing one probe on the outside of the plug and the other on the inside of the
plug. Voltage measurement should read 18-32VAC. If no voltage is present, replace the transformer
supplying power to the ActivePure
2. Leave unit attached to ducting. Remove (4) Phillips head screws from the cover of the unit. Remove
the cover. Unplug the black and white wires from the ballast. Check incoming voltage by placing
Multimeter probes on the two exposed wires. Voltage measurement should be between 18-32VAC.
If there is no voltage reading, power is not supplied to the unit. Check power source and verify
Induct Safety Switch is fully depressed. Safety switch plunger is located underneath the unit and is
depressed when unit is secured to mounting plate.
3. Re-plug the black and white wires to the ballast.
4. Remove unit from the duct by taking off the (4) 11/32 thumb
nuts that secure the unit to the mounting plate.
5. Remove the (2) Phillips head screws that hold the cell
assembly in place. Remove the UV lamp from the 4-pin
connector by placing a small flat head screwdriver between
the 4-pin connector and the UV lamp base. Gently pry and
lift up on the Cell until the UV lamp is unseated from the
4-pin connector, remove the Cell Assembly.
INDUCT GUARDIAN I (Model: B1013U)
®
Induct Guardian I.
®
Induct
®
11