Before Installing the Valve:
1. To mount the valve on the actuator, place the O-ring on the valve in the circular indentation around the stem.
2. Use a thin metal object that fi ts in the valve stem groove to turn the valve and adjust it so that it is aligned with
the actuator.
3. Once the valve is aligned and in place, put the clip on the four pins such that the curve is on the inside of all four posts.
4. Make sure the Water Control Panel wiring matches the wiring diagram on page 3.
•
To access the board, remove the four screws on the front of the Water Control Panel, remove the bottom and
fl ip the front panel so that the back is facing up.
5. Plug the Water Control Panel into a standard outlet. KEEP FINGERS AND OTHER OBJECTS AWAY FROM VALVE TO
AVOID INJURY. You should hear the actuator turn the valve one full cycle.
WARNING: The FOLLOWING STEP WILL DELETE any and all Sensors previously addressed to the Control
Panel. All Sensors will need to be re-addressed (See Installing and Testing Sensors section) to the
Control Panel.
6. Reset the Water Control Panel to the factory settings pressing the "MODE" button and while still depressing this
button, also depress the "OPEN" button and HOLD BOTH BUTTONS until the screen changes.
7. Release fi rst the "OPEN" button and then the "MODE" button.
8. Press the "CLOSE" button to reset to factory default.
9. Test the actuator by removing the rubber stops at both ends of the valve and checking to see the valve position. The
indicator lights on the Water Control Panel should show the correct current position of the valve.
10. Change valve position by pressing the unlit "OPEN" or "CLOSE" button. Press the unlit indicator, either "OPEN" or
"CLOSE", whichever one does not have a lit light next to it to tell the actuator to perform one-half cycle. KEEP FINGERS
AND OTHER OBJECTS AWAY FROM VALVE TO AVOID INJURY.
11. Visually verify that the valve has changed position.
12. Repeat steps 10-11 a few times by pressing the alternating UNLIT button "OPEN" or "CLOSE" to test and exercise the
valve and actuator.
13. You are now ready to install the valve. Please refer to the "Valve Installation" section of the Instruction Manual for
detailed instructions for various methods of installation.
Installing and Testing Sensors
Hardwired Sensor Probes
1. To install hardwired sensor probes (WPSC), fi rst ensure that power is disconnected to the Water Control Panel.
2. Open the case for the Water Control Panel and note the side circuit board with one long terminal strip going
the full length.
3. Wire the desired number of sensor probes into the terminal strip matching the leads of the wire with the paired
off terminals as marked by the writing on the circuit board.
4. If the wires are in the wrong terminals, the sensor probe will not work.
5. Once you have wired the desired number of sensor probes into the terminal strip, close the case and
replace the screws.
6. Plug the Water Control Panel into a standard outlet and wait for it to beep indicating it has fi nished its boot
up sequence.