Port Connections

■ Port speci昀椀cations
• Be sure to check the port speci昀椀cations below before connecting the device. Prepare a cable that complies with the protection rating IP67.
Ethernet port
M12 (Socket-Female), 4-pin,
D-coded
Type
Push-Pull
Number of ports
Tightening torque
0.6 N m
Daisy chain
Supported function
• The example of communication cable for the PDCT port
Connector 1
5-pin
M12 (Plug-Male)
2
1
5
3
4
01. Connect to the PROFINET
02. Connect the IO-Link devices
᜸ The maximum output current is 2 A at each I/O port. Con昀椀gure the device so that the total current of the I/O ports does not exceed 9 A.
᜸ Check the wiring information in the manual of the IO-Link device to be connected.
I/O port
M12 (Socket-Female), 5-pin,
A-coded
YES
YES
8
2
0.6 N m
-
Wiring
Connector 2
Connector 1
Pin no.
USB Type A
1
2
1 2
3
4
3
4
5
01. Connect the M12 connector to the Ethernet port. See the connections below.
02. Connect the connector to the PROFINET network.
03. Put the waterproof cover on the unused port.
01. Connect the M12 connector to the I/O port. See the connections below.
02. Put the waterproof cover on the unused port.
PDCT port
M12 (Socket-Female), 5-pin,
A-coded
YES
1
0.6 N m
USB serial communication
Connector 1
Connector 2
Connector 2
Function
Pin no.
Function
N.C.
+ 5 VDCᜡ
1
Data -
→ 2
Data -
0 V
→ 4
0 V
N.C.
-
-
Data +
→ 3
Data +
Transmit Data +
1
TX +
Receive Data +
2
RX +
TX -
Transmit Data -
3
RX -
Receive Data -
4
• Network device: PLC or PROFINET device supporting PROFINET protocol
+24 VDCᜡ
1
I/Q: Digital Input
1
2
2
3
C/Q: IO-Link, Digital Input/Output
5
4
Not Connected (N.C.)
4
3
5
Power supply port
Input: 7/8" (Plug-Male), 5-pin
Output: 7/8" (Socket-Female), 5-pin
N.A
2
1.5 N m
Daisy chain
0 V