Quick Start Guide
GFK-2837A
Shield to
connector
CANopen Cable
The cable shield should be connected to each device on the network.
Network Data Rates and Bus Lengths
The CNM001 module supports the estimated bus lengths and data
rates defined in CiA 303 version 1.8.0. For performance details, refer to
the PACSystems RX3i CANopen Master Module User's Manual, GFK-2831.
Network Termination
A 120 ohm termination resistor is required at the
each end of the bus. Where termination is
required, you must use a bus terminal with built-
in selectable termination.
Hardware Installation
Section 2
Sep 2019
CAN_L (pin 2)
CAN_H (pin 7)
CAN GND (pin 3)
7