AutoPulse Z-20 Schnellstart-Handbuch
Blättern Sie online oder laden Sie pdf Schnellstart-Handbuch für Sicherheitssensoren AutoPulse Z-20 herunter. AutoPulse Z-20 2 Seiten.
UL, ULC, CSFM Listed;
FM Approved*
Features
Provides Temporal Code 4 (TC4) NAC
(Notification Appliance Circuit) control for
Carbon Monoxide (CO) gas warning:
• The TC4 CO gas warning is a repeated sequence of
four cycles of 100 msec on with 100 msec off,
followed by 5 seconds off per NFPA 720, Standard
for the Installation of Carbon Monoxide (CO)
Warning Equipment in Dwelling Units
• Compatible appliances includes: CO Sounder Bases
4098-9771 and 4098-9798, 4901-9820 Horn (set for
free-run), 49CMT Series multi-tone horns (set for
free-run horn tones), and 4903 Series 4-wire A/V
appliances horn input (not compatible with SmartSync
horn control appliances)
Compatible equipment NAC sources:
• AUTOPULSE Z20
• Simplex 4007ES Hybrid, 4010ES, 4100ES, and
4100U NAC outputs
• 4009 IDNet NAC Extender NAC outputs
• Each module requires an input NAC that powers the
3A rated output NAC for control of compatible
audible notification appliances only (not for strobes)
Three selectable operation modes:
• Synchronized operation allows a separate and
dedicated control NAC to both activate and
synchronize the Temporal Code 4 output timing of up
to 20, 4905-9835 modules
• Unsynchronized operation also allows the separate
and dedicated control NAC to activate the Temporal
Code 4 output timing of up to 20, 4905-9835 modules,
but without synchronization between the modules
• Stand-Alone operation allows the input NAC in
alarm to activate Temporal Code 4 timing for NACs
dedicated for CO gas alarm; no fire alarm signals are
available, no control NAC is used
• For both Synchronized and Unsynchronized modes,
when the control NAC is off, the module output NACs
will follow the fire alarm signals of the input NAC
• NOTE: For TC4 output, both the input NACs and the
control NACs requires a Steady On signal
Compact, sealed construction:
• Mounts in standard 4" square electrical box
• Compatible with Adapter Plate 4090-9813 to fit
⁄
11
4
" (119 mm) square electrical boxes
16
• Screw terminals for wiring connections
Listed to UL 864 and ULC S527
Description
CO gas alarm warnings are required to be different from
fire alarm warnings. In the event of a CO gas alarm, the
presence of a Temporal Code 4 audible signal pattern
identifies the type of condition to the responders to assist in
determining the proper actions to be taken.
Non-Addressable Peripherals
4905-9835 Temporal Code 4
Module for CO Gas Alarm Notification
4905-9835 Temporal Code 4 Module
(shown approximately 1/2 size)
Description (Continued)
CO gas alarm, or fire alarm. Use of the 4905-9835
Temporal Code 4 Module allows the NFPA 720 Temporal
Code 4 signal to be generated using a standard Steady On
audible appliance NAC input. Under the fire alarm panel's
control, the audible notification signal can be selected for a
conventional fire pulse pattern for a fire alarm condition, or
the Temporal Code 4 pattern can be activated for a CO gas
alarm condition.
Specifications
For 24 VDC NACs, up to 3 A
maximum, limited by input NAC
NAC Control
rating; for control of audible
notification appliances compatible
with TC4 code pulse duty cycle
Supervisory current = 0.18 mA
Input NAC Current
Requirements
Alarm current = 15 mA
Supervisory current = 0 mA
Control NAC Current
Requirements
Alarm current = 3 mA
Mounting Distance
Mount close-nippled, 20 ft (6 m)
to input NAC Source
maximum distance
Screw terminals for in/out wiring,
Wire Connections
18 to 12 AWG wire
(0.82 to 3.31 mm
4" x 4 ⅛" x 1 ⅜" D
Dimensions
(102 mm x 105 mm x 35 mm)
Mounting Plate
Sheet metal, galvanized
Material
32° to 120° F (0° to 49° C),
Temperature Range
intended for indoor operation
Humidity Range
Up to 93% RH at 100° F (38° C)
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:328
for allowable values and/or conditions concerning material presented in this document. This
product was not accepted by MEA (NYC) as of document revision date. Additional listings
may be applicable; contact your local Simplex product supplier for the latest status. Listings
and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection
Products.
1
2
ON
2
)
T-2016293-1 10/2016