Gallagher C305401 Hinweise zur Installation - Seite 6

Blättern Sie online oder laden Sie pdf Hinweise zur Installation für Kartenleser Gallagher C305401 herunter. Gallagher C305401 12 Seiten. Reader
Auch für Gallagher C305401: Hinweise zur Installation (12 seiten)

Gallagher C305401 Hinweise zur Installation
HBUS
Device
Terminate
Cable distance
Cable type
CAT 5e or
better**
BELDEN 9842**
(shielded)
SEC472
SEC4142
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for optimal HBUS RS485 performance.
Notes:
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
If other cable types are used, operating distances and performance may be reduced
depending on the cable quality.
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to function correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
"T" or "Star" circuits are
HBUS
not permitted between
Device
HBUS devices
Controller 6000
H1
HBUS
H5
Device
HBUS Module
HBUS
Device
Terminate
Cable format*
HBUS
single reader
connected using
data only in a
single cable
4 twisted pair
500 m (1640 ft)
Each 2 x 0.2 mm
2
(24 AWG)
2 twisted pair
500 m (1640 ft)
Each 2 x 0.2 mm
2
(24 AWG)
4 x 0.2 mm
400 m (1310 ft)
2
Not twisted
pairs (24 AWG)
4 x 0.4 mm
400 m (1310 ft)
2
Not twisted
pairs (21 AWG)
H4
H8
HBUS
Device
HBUS
Device
Terminate
Cardax IV
single reader
connected using
data only in a
single cable
200 m (650 ft)
200 m (650 ft)
200 m (650 ft)
200 m (650 ft)
HBUS
Device
Terminate
HBUS/Cardax IV
single reader
connected using
power and data
in a single cable
100 m (330 ft)
100 m (330 ft)
100 m (330 ft)
150 m (500 ft)
Page 6