Emerson Network Power NetSure 701 A41-S1 Benutzerhandbuch - Seite 17
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Stromversorgung Emerson Network Power NetSure 701 A41-S1 herunter. Emerson Network Power NetSure 701 A41-S1 20 Seiten. Subrack power system
Note
1. Tighten the captive screw of the MFU and DU Panel by the cross head screwdriver when there is no operation.
2. Also tighten the handle of the 501 modules by the cross head screwdriver.
3. Please plug in the new modules or installing a new panel after removing the rectifier module.
2.4 Electrical Installation
2.4.1 Power System Cabling Method
Cabling from the top of the power system
DU unit and MFU unit are available for the system top cover cabling.
For DU unit cabling: Cabling from the cable outlet area and then fixed to the cable-bundling plate and the top edge.
As shown in Figure 2-9.
NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Figure 2-7 Installation size of NetSure 701 A41- S4 (unit: mm)
438.5
482.6
Figure 2-8 Installation size of NetSure 701 A41-S5 (unit: mm)
Chapter 2 Installation Instruction
265.0
9