AGS Merlin 1000Si Benutzer- und Installationshandbuch - Seite 6
Blättern Sie online oder laden Sie pdf Benutzer- und Installationshandbuch für Controller AGS Merlin 1000Si herunter. AGS Merlin 1000Si 9 Seiten. Gas safety products, gas utility controller
Auch für AGS Merlin 1000Si: Benutzer- und Installationshandbuch (7 seiten), Handbuch für Installation und Betrieb (16 seiten), Benutzerhandbuch (12 seiten)
Merlin 1000Si
Gas Utility Controller
EM STOP
If an emergency shut off button (either remote or on the panel) is pressed, the LED will
illuminate and the gas will be shut off. The EM Stop button must be re-set before restarting the
system.
OFF = OK
AMBER = EM Stop button pressed
GAS DETECTED
Under normal working conditions this LED is off.
If the external Merlin detector connected detects gas this will illuminate and the gas valve will
shut off.
OFF = OK
RED = Gas detected.
CO2 HIGH
Under normal working conditions this LED is off.
If the concentration of CO
will illuminate and the gas valve will shut off.
OFF = OK
RED = the concentration of CO
3.3
EMERGENCY SHUT OFF
The Emergency shut off button is located on the front of the panel. There is also a facility for
remote shut off buttons to be wired in series.
The Emergency shut off button(s) will cut off the gas supply when activated.
To reinstate the system, the Emergency shut off button(s) will need to be reset and the panel
restarted.
3.4
BUILDING MANAGEMENT SYSTEM INTERGRATION
The Merlin 1000Si can be integrated with a BMS to make or break a circuit on gas on/gas off,
(valve open or valve closed). This will tell the BMS whether or not power is being sent to the
solenoid.
There is a dip-switch located on the inside facia of the Merlin 1000Si labelled [BMS SELECTION].
This is factory set in the 'off' position which signals the BMS on gas on/gas off.
When switched to the 'on' position, the 1000Si will only signal the BMS on a fault, i.e. CO2 high
level detected, gas detected, EM Stop pressed, etc.
3.5
FIRE ALARM INTERGRATION
The Merlin 1000Si can be integrated with a fire alarm to shut the gas supply automatically in the
event of a fire. The volt free fire alarm signal can be wired in series with any remote emergency
shut off buttons.
Rev: 04 Date: 22-10-18
in the air is at alarm level (relevant detector required), the LED
2
is at alarm level.
2
User & Installation Manual
6