Installation & Operation Manual

Accessing Gas Detector Information

To access individual detector information - Press the 'DETECTORS'
button on screen during any system condition.
If a detector reaches alarm level, the ID will be shown in the top left
hand corner of the screen, if more than one detector reaches
alarm, the ID shown will be the detector that signals the alarm first.

Detector(s) Screen Page Overview

Switch between pages by touching the relevant page button. Each page can display up to 4
detectors as follows:
a.
ID
The detector identification number (configured
via dip switches on the detector circuit board).
b.
Serial Number
The unique serial number for that detector.
c.
Gas
The target gas that the detector is monitoring.
d.
Status
The status of gas levels, errors and messages.
e.
Value
The concentration value of gas detected.
To return to the main screen, press the HOME button on screen.

Detector(s) Status Overview

GOOD
o
PRE ALARM
o
ALARM
o
FAULT
o
END OF LIFE
o
SERVICE
o
-- X --
o

Gas Level Thresholds

Gas Type
Carbon Monoxide (CO)
Nitrogen Dioxide (NO
For more information refer to your Parksafe detector manual.
AGS Parksafe - IOM Iss: DRAFT 3 06-20
Gas levels are safe / No error conditions.
Gas detected has reached pre-alarm levels.
Gas detected has reached alarm levels.
Gas sensing module issue.
The gas sensing element has reached the end of its expected lifecycle.
Gas sensing element requires bump test/ service.
Detector signal lost, not installed or not configured correctly.
GOOD Level
0 - 25 ppm
)
0 - 0.7 ppm
2
Parksafe Control Panel
PRE-ALARM Level
25 -100 ppm
0.7 - 2 ppm
ALARM Level
+ 100 ppm
+ 2 ppm
9