AGS Parksafe Control Panel Handbuch für Installation und Betrieb - Seite 9
Blättern Sie online oder laden Sie pdf Handbuch für Installation und Betrieb für Controller AGS Parksafe Control Panel herunter. AGS Parksafe Control Panel 16 Seiten. Ventilation control panel
Auch für AGS Parksafe Control Panel: Handbuch für Installation und Betrieb (16 seiten), Installation, Betrieb und Wartung (16 seiten), Handbuch für Installation, Betrieb und Wartung (20 seiten)
Installation & Operation Manual
Accessing Gas Detector Information
To access individual detector information - Press the 'DETECTORS'
button on screen during any system condition.
If a detector reaches alarm level, the ID will be shown in the top left
hand corner of the screen, if more than one detector reaches
alarm, the ID shown will be the detector that signals the alarm first.
Detector(s) Screen Page Overview
Switch between pages by touching the relevant page button. Each page can display up to 4
detectors as follows:
a.
ID
The detector identification number (configured
via dip switches on the detector circuit board).
b.
Serial Number
The unique serial number for that detector.
c.
Gas
The target gas that the detector is monitoring.
d.
Status
The status of gas levels, errors and messages.
e.
Value
The concentration value of gas detected.
To return to the main screen, press the HOME button on screen.
Detector(s) Status Overview
GOOD
o
PRE ALARM
o
ALARM
o
FAULT
o
END OF LIFE
o
SERVICE
o
-- X --
o
Gas Level Thresholds
Gas Type
Carbon Monoxide (CO)
Nitrogen Dioxide (NO
For more information refer to your Parksafe detector manual.
AGS Parksafe - IOM Iss: DRAFT 3 06-20
Gas levels are safe / No error conditions.
Gas detected has reached pre-alarm levels.
Gas detected has reached alarm levels.
Gas sensing module issue.
The gas sensing element has reached the end of its expected lifecycle.
Gas sensing element requires bump test/ service.
Detector signal lost, not installed or not configured correctly.
GOOD Level
0 - 25 ppm
)
0 - 0.7 ppm
2
Parksafe Control Panel
PRE-ALARM Level
25 -100 ppm
0.7 - 2 ppm
ALARM Level
+ 100 ppm
+ 2 ppm
9