AGS Parksafe Control Panel Installation, Betrieb und Wartung - Seite 12

Blättern Sie online oder laden Sie pdf Installation, Betrieb und Wartung für Bedienfeld AGS Parksafe Control Panel herunter. AGS Parksafe Control Panel 16 Seiten. Ventilation control panel
Auch für AGS Parksafe Control Panel: Handbuch für Installation und Betrieb (16 seiten), Handbuch für Installation und Betrieb (16 seiten), Handbuch für Installation, Betrieb und Wartung (20 seiten)

AGS Parksafe Control Panel Installation, Betrieb und Wartung
Installation, Operation & Maintenance
Silence & Reset
To silence the internal buzzer – press the Silence button on the front panel.
This will also silence any external audio sounders connected to the panel.
If the system reaches alarm condition – the panel will need to be reset when the gas levels detected return
to a safe level.
Check the detector status pages to identify where gas has been detected and if levels have returned to a
safe condition before resetting the system.

Accessing Gas Detection Information

To access detector status screens press the 'Gas Detection' section on screen any time.
Switch between pages by touching the relevant page button.
Each page can display up to 4 detectors as follows:
a.
The ID configured via switches on each detector board.
b.
The unique serial number for that detector.
c.
The target gas that detector is monitoring.
d.
The status of gas levels, errors and messages.
e.
The concentration value of gas detected.
To return to the main screen, press the home button on screen.

Detector Status

GOOD
PRE ALARM
ALARM
FAULT
END OF LIFE
SERVICE
-- X --

Gas Detector Alarm Set Points

▲Rising alarm ▼Falling alarm PPM (Parts per Million)

Modbus Communication Rescan

At any time, the user can rescan and refresh the Modbus communication data if there is a bad connection
in the chain by pressing the icon on screen. When pressed the system will search for all signals connected
to the panel i.e. gas detectors without the need to reset the system.
Rev: 13
0721
Gas levels are safe / No error conditions.
o
Gas detected has reached pre-alarm levels.
o
Gas detected has reached alarm levels.
o
Gas sensor module has an issue (Removed or not properly installed) or service required.
o
The gas-sensing element has reached the end of its expected lifecycle.
o
Gas sensing element requires periodic bump test/service.
o
Detector signal lost, not installed or not configured correctly.
o
Gas Detector
Carbon Monoxide (CO)
Nitrogen Dioxide (NO2)
Parksafe Control Panel
Pre-Alarm
Alarm State
▲ 25ppm
▲ 100ppm
▲ 0.7ppm
▲ 2.0ppm
12