AGS Parksafe Control Panel Installation, Betrieb und Wartung - Seite 15

Blättern Sie online oder laden Sie pdf Installation, Betrieb und Wartung für Bedienfeld AGS Parksafe Control Panel herunter. AGS Parksafe Control Panel 16 Seiten. Ventilation control panel
Auch für AGS Parksafe Control Panel: Handbuch für Installation und Betrieb (16 seiten), Handbuch für Installation und Betrieb (16 seiten), Handbuch für Installation, Betrieb und Wartung (20 seiten)

AGS Parksafe Control Panel Installation, Betrieb und Wartung
Installation, Operation & Maintenance
STEP 2.
Ensure you have the correct gas for the device type prior to application.
Screw the regulator/valve into the gas cylinder outlet.
Once sealed, the regulator pressure gauge (if available) will indicate cylinder pressure.
Offer up the applicator hose/cone and fully cover the sensing element on the front case.
Open the valve/regulator to allow the gas to be delivered at a pre-set flow rate.
Apply gas.
The detector Alarm LED will illuminate at the alarm set point.
The Parksafe control panel will activate all configured outputs/relays (unless service
mode is activated) and will display the gas concentration detected.
Remove applicator hose/ cone and turn the gas cylinder regulator/valve off.
Wait for detector to stabilise / return to normal.
Reset the service reminder by shorting out the unmarked header on the detector board.
Test complete.
Record your test details.
Always remove the regulator/valve after use - All cylinders will re-seal upon removal of the regulator!
Never use expired or 'near empty' gas cylinders!
Always give at least five (5) minutes between testing the same unit or until gas has fully dispersed!
Always consider safety and use equipment in accordance with Safety Data Sheets!
If Service mode is activated – reset the system after completing the bump tests!
Pressing silence on the panel will silence the internal buzzer when in alarm!

Specification

General
Product:
Indicators (4.3" Touch Screen)
Screen Brightness
Mounting
Electrical
Max. Power Consumption
Power Voltage Input Range
Outputs
Communication
Relay(s)
Terminal Wire ratings
Fuse
Construction
Dimensions (H x W x D)
Unit Weight (Approx.)
Housing Material
Environmental
Ingress Protection
Storage Conditions
Operating Conditions
Compliance
CE
Rev: 13
0721
PARKSAFE Ventilation Controller
Main Zone Status. ID. Gas Type. Outputs. Concentration Level. Measured Value. End of Life. Fault. Service.
Adjustable 0-100%
Wall Mounting
14.5W
100-240vac
Ventilation System Outputs x2 / Alarm / Damper / Parksafe Detector / Sounder/Strobe / 24vdc / 0-10vdc
RS485 MODBUS RTU
4x 120vac 6A Max (Non Latching Switch) 1x24vdc
Copper 18AWG (0.75mm2) Min. 25 x screw terminals.
3.15A
180 x 255 x 77 mm/ 7.08 x 10.03 x 3"
1.1kg / 38.8oz
Polylac - PA765
IP65 (Pre-installation)
Dry. Cool. Flat
-10 ~ 50°C / 14 ~ 122°F 30 ~ 80% rf
EN 61326-1 / BS EN IEC 61010-1
Parksafe Control Panel
15