The assembly method for the anticontamination valve is shown in the following figure:

4.3 OPERATION

The antipollution check valves shall be operated according to the requirements for check valves,
in the orientation shown in the recommended installation orientation diagram. It is recommended to periodically
purge the valve with fresh water (once a year) to assure full performance. Hard solids with the size above 1mm
should be filtered out of the transmitted medium by an upstream filter to prevent seizure of the poppet gear and
damage to the seals.
Install cut-off valves upstream and downstream of the valve to allow maintenance.
Install the valve horizontally with its drain valve downwards;
connect the drain valve to a drainage system (sewage pipework or drain gullies) with a minimum of 20 mm of air
gap between the top edge of the drain line and the drain valve outlet. A filter should be installed directly
upstream of the valve. The installation site and method shall assure free access for maintenance and servicing.
Do not install the valve in a location exposed to flooding.
The product shall not be exposed to temperatures outside of the permissible operating range.
Overrunning the valve operating limits may damage the valve
and the manufacturer's suretyship liability shall not apply.

4.4 OCCUPATIONAL HEALTH AND SAFETY

The antipollution check valves are eligible for
the OHS guidelines and recommendations concerning installation of pipelines and devices for: water supply
stations, heat power plants, water treatment plants, sewage treatment plants, pumping stations and other
facilities, and eligible for the Polish Regulation concerning general OHS laws (use of personal protective
equipment for hands, legs and head, and safety garment), especially at work with low or high temperature
hazard.
Misuse of this product is prohibited.

5 WARRANTY TERMS AND CONDITIONS

The product assembled, installed and operated in compliance with this Manual is covered by a commercial
warranty from the manufacturer.
The warranty terms, conditions and period are specified in the relevant Warranty Sheet.
OPERATION AND MAINTENANCE MANUAL
01-2016
11