Gree Versati II Series Handbuch - Seite 8
Blättern Sie online oder laden Sie pdf Handbuch für Wärmepumpe Gree Versati II Series herunter. Gree Versati II Series 13 Seiten. Air-to-water heat pump monobloc versati
Auch für Gree Versati II Series: Service-Handbuch (18 seiten)
Design & Selection
Correct Design
5) Distance between the unit and the water trap (collector) should be within 15m. If the distance exceeds
20m, then it is required to calculate the hydraulic power.
4.2 Requirements on Installation of the Water Trap (Collector)
1) The water trap (collector) should be installed on the wall or inside the special box. For housing
constructions, it is generally installed in the kitchen.
2) The valve for the water trap (collector) should be installed horizontally and keep a distance of at least
300mm to the ground.
3) The water supply valve should be installed upstream of the water trap (collector) and the return valve
should be installed downstream of the water trap (collector)
4) A filter is required upstream of the water trap (collector).
B
2F
1F
B
6