Majestic 32LCUF-R Installations- und Betriebsanleitung - Seite 7

Blättern Sie online oder laden Sie pdf Installations- und Betriebsanleitung für Innenkamin Majestic 32LCUF-R herunter. Majestic 32LCUF-R 20 Seiten. Lo-rider unvented vent-free fireboxes

GENERAL INSTALLATION INFORMATION

MINIMUM HEARTH DIMENSIONS

32LCUFF
A
22⅜"
B
1¾"
C
28⅝"
D
8"
E
23¼"

LOCATION OF FIREBOX

Carefully select the best location for installation of your
vent-free firebox. The following factors should be taken
into consideration:
• Clearance to side wall, ceiling, woodwork and
windows. See "Clearances/Height Requirements on
page 8. Minimum clearances to combustibles must
be maintained.
• Location must not be affected by drafts caused by
kitchen exhaust fans, ceiling fans, return air registers
for forced air furnaces / air conditioners, windows or
doors.
• Installation must provide adequate ventilation and
combustion air.
• DO NOT INSTALL THIS FIREBOX IN A BED-
ROOM OR BATHROOM.
• Location should be out of high traffic or windy or
drafty areas.
• DO NOT INSTALL WHERE CURTAINS, FURNITURE, CLOTHING OR OTHER FLAMMABLE OBJECTS
ARE LESS THAN 42" FROM FRONT OF HEATER.
• Never obstruct the front opening of the vent-free firebox or restrict the flow of combustion and ventilation air.
• Minimize modifications to existing construction. Refer to Figure 3 below for location suggestions.
• Do not install in the vicinity where gasoline or other flammable liquids may be stored. The vent-free firebox must be
kept clear and free from these combustible materials.
26D4751
36LCUFC-R
25⅞"
15"
½"
0¼"
25⅝"
LOCATION OF FIREBOX
and
Figure 2 - Minimum Hearth Dimensions
Figure 3 - Location of Firebox
7