Gamewell MS-7S Betriebsanleitung - Seite 2

Blättern Sie online oder laden Sie pdf Betriebsanleitung für Rauchmelder Gamewell MS-7S herunter. Gamewell MS-7S 2 Seiten.

MS-7S Single Action Station
The MS-7S single action station is used with conventional
fire alarm control panels. It features a set of single pole
contacts and wire leads for connection to an initiating cir-
cuit.
MS-7SP Double Action Station
The MS-7SP is a double action station similar to the MS-7
station, with the additional feature of both English and
Spanish instructions molded into the unit.
MS-7LOB Double Action Station
(Listed for Outdoor Applications)
The MS-7LOB station must be mounted on a Model SB-I/O
backbox. In retrofit applications, the station is UL Listed for
use with the WP-10 backbox. It is intended for use with
conventional control panels and has a set of single pole
contacts and screw terminals.
Mounting
The MS-7 interior stations may be surface mounted (use
backbox SB-I/0) or semi-flush mounted on a standard dou-
ble-gang, or 4-inch (10.2 cm) square electrical box. An
optional trim ring (BG-TR) may also be used for semi-flush
mounting.
NYC-Plate
The NYC-Plate provides the backplate for the manual pull
station. (See Figure 1).
Figure 1 NYC-Plate
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0616 Rev. B2 page 2 of 2

Specifications

Material:
Contact Ratings:
Dimensions:
Operating
Temperature (MS-7AF): 32° to 120° F (0° to 49° C)
Relative
Humidity (MS-7AF):
Alarm Current:
Supervisory Current
(MS-7AF):

Ordering Information

Model
MS-7
MS-7AF**
MS-7ASF
MS-7S
MS-7SP
MS-7LOB
SB-I/O
SB-10
BG-TR.
NYC-Plate
**For use with Gamewell-FCI analog addressable control
panels only.
GAMEWELL-FCI
www.gamewell-fci.com
®
Lexan
0.25 amps. @ 30 VAC/VDC
(resistive)
5 5/8" H x 4 1/4" W x 1 1/4" D
(14 x 10.1 x 3.2 cm)
10 to 93% (non-condensing)
.0030 amp. 0.007 for LED
.00030 amps.
Description
Double action station.
Velociti addressable double
action station.
Velociti addressable single action
station
Single action station, wire leads.
Double action station, English
and Spanish instructions.
Double action station, outdoor
use. (Must use SB-I/O - Indoor/
outdoor use backbox).
Indoor/outdoor use backback-
box.
Surface backbox.
Trim ring for semi-flush mount
NYC backplate for manual pull
station