ADF LINEA 100 Montageanleitung Handbuch - Seite 5
Blättern Sie online oder laden Sie pdf Montageanleitung Handbuch für Innenkamin ADF LINEA 100 herunter. ADF LINEA 100 16 Seiten. Nmv inbuilt heater zero clearance box supplement instructions
ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Dimensions for Heat Resistant board:
300mm
above ZCB
• Non-Combustible Board – Fibre Cement Sheet of 18mm thick to prevent
cracking, (as used in Test) or Skamol Board 40mm.
• Fix with separate sheets top and bottom, and use separate off cuts on each
side. Use the factory cut neat edge to face the heater opening, if not
covering with optional frame or tiling.
Must leave a 5mm gap between each edge of the heater and the non-
combustible board to allow for metal expansion.
1320mm to 45mm stud centres.
1275mm opening
1/1/21
1420mm
5