3.3. Settings menu
You can reach the settings menu from the operating menu as indicated in section 3.2.2. The displays of the settings menu
(sections 3.3.1.–3.3.26.) can be scrolled with the scrolling buttons (see section 3.1., items 5 and 6 in the figure).
3.3.1.
Setting the basic fan speed
MIN speed
1
3.3.2.
Moving to the operating menu
To main menu
Press + and -
3.3.3.
Erasing the week programme
Erase week prog.
Press + and -
3.3.4.
Week programme programming
Adjust week prog.
Press + and -
3.3.5.
Adjusting time
Adjust time
Press + and -
3.3.6.
Mode of operation of the maximum speed setting
MAX Speed limit
with adjustments
3.3.7.
Choosing the language version
Kieli / Language
English
3.3.8.
Restoring factory settings
Factory settings
see manual
3.3.9.
Adjustment interval
Adjust interval
10
3.3.10. Resetting the service reminder
Mainten. reset
Press + and -
3.3.11. Contrast of the control panel display
Display contrast
05
3.3.12. Address of the control panel
Panel address
1
3.3.13. Adjusting the direct current fan on the extract air side
DC fan exhaust
100%
DV 90 SE
INSTRUCTIONS FOR USING THE CONTROL PANEL
The desired basic fan speed (minimum fan speed) is selected with the + and – buttons. Active when
week clock control is not on. Week clock control changes this speed.
You can return to the operating menu by pressing the + and – buttons simultaneously.
The week programme can be totally erased by simultaneously pressing the + and – buttons.
You can access the programming mode for the week clock programme by simultaneously pressing
the + and – buttons. See section 3.4.1.
You can adjust time by simultaneously pressing the + and – buttons. For more details, see section
3.4.2.
The maximum fan speed setting can be selected to be active either in connection with (carbon dioxide
and humidity) adjustments or permanently. The selection is done with the + and – buttons.
Select the desired language (German, English, Swedish, French or Finnish) with the + and – buttons.
The general factory settings can be restored by pressing the + and – buttons simultaneously.
Remember to ensure that the setpoints are in accordance with the factory settings for this unit.
Especially, check the unit model (electricity / water) and change if needed as stated in section
3.3.20.
The adjustment interval for humidity and carbon dioxide adjustments is selected with the + and –
buttons. The adjustment interval refers to minutes.
The maintenance reminder is reset by pressing the + and – buttons simultaneously. This
turns out the maintenance reminder symbol ( ) in the main display.
The contrast setting for the control panel display is changed with the + and – buttons.
The address of the control panel is changed with the + and – buttons. Two control panels cannot
have the same address. If control panels have the same address, they will go to the bus fault state
and will not operate.
The desired adjustment value for the DC fan is selected with the + and – buttons. The rotation speed
of the extract air fan can be lowered by decreasing the percentage value. If the unit has alternating
current fans, this adjustment has no impact on the operation of the unit.
9