IKEA IHI8304WS0 Installationsanleitung und Gebrauchs- und Pflegeanleitung - Seite 5
Blättern Sie online oder laden Sie pdf Installationsanleitung und Gebrauchs- und Pflegeanleitung für Lüftungshaube IKEA IHI8304WS0 herunter. IKEA IHI8304WS0 28 Seiten. 30" (76.2 cm) island canopy range hood
Installation Clearances
i
B
l
D
1
E
!
m
i
C
A. Ceifing height
B. Countertop
height
C. Preferred hood height: 30" to 36" (76.2 cm to 91.4 cm)
is recommended.
D. Hood height from ceiling to bottom of the hood:
A-B-C=D
E. D-13/4" (4.4 cm) chimney assembly height
IM PORTANT:
Confirm that the dimension (D) is within the minimum to
maximum dimensions. See "Product Dimensions."
Vent system must terminate to the outside, except for non-
vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed
area.
Do not use 4" (10.2 cm) laundry-type wall caps.
Use metal vent only. Rigid metal vent is recommended.
Do
not use plastic or metal foil vent.
The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the range
hood.
For the most efficient and quiet operation:
•
Use a straight run or as few elbows as possible.
•
Use no more than three 90 ° elbows.
•
Make sure there is a minimum of 24" (61.0 cm) of straight
vent between the elbows if more than 1 elbow is used.
•
Do not install 2 elbows together.
•
Use vent clamps to seal all joints in the vent system.
•
Use caulking to seal exterior wall or roof opening around the
cap.
•
The size of the vent should be uniform.
Cold Weather
Installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction
of outside temperatures
as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup
Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
This island hood is factory set for venting through the roof.
An 8" (20.3 cm) round vent system is needed for installation (not
included). The hood exhaust opening is 8" (20.3 cm) round.
NOTE: Flexible vent is not recommended.
Flexible vent creates
back pressure and air turbulence that greatly reduce
performance.
Vent system can terminate either through the roof or wall. To vent
through a wall, a 90 ° elbow is needed.
Rear discharge
A 90° elbow may be installed immediately above the hood.
For Non-Vented
(recirculating)
Installations
If it is not possible to vent cooking fumes and vapors to the
outside, the hood can be used in the non-vented
(recirculating)
version, using the optional deflector and charcoal filter kits. To
order, see the "Assistance
or Service" section.
Non-vented (recirculating)
Roof Venting
A. Deflector
B. 8" (20.3 cm) round vent
A. Roof cap
B. 8" (20.3 cm) round vent