FIGURE 5 - Junction Box
NOTE: Electric heated units may be provided with a line voltage
thermostat. Mount and wire thermostat according to instructions
and the wiring diagram.
E. Install the cover housing and attach it temporarily at each end of the
unit with two of the cover screws provided. Final assembly should be
done after airflow adjustments. See Figure 6.
F. Switch on the power at the service disconnect. Turn on the unit and
check the sequence of operation against the wiring diagram.
G. Proceed to Section VI - MECHANICAL CONNECTIONS for electric
heated units, otherwise proceed to
Section VII - AIRFLOW ADJUSTMENTS
VI. MECHANICAL CONNECTIONS
A. ELECTRICALLY HEATED MODELS
The heater circuit may be controlled by a remote thermostat, or
manually through a remote mounted three position - fan only/off/
fan with heat switch. Overheating protection is provided by auto
reset thermal cutouts built into the blower assembly (see wiring
diagram). Proceed to Section VII - AIRFLOW ADJUSTMENTS.
Model
KW
AS/ST*1036E
7.5
AS/ST*1042E
7.5
AS/ST*1048E
7.5
AS/ST*1060E-2
7.5
AS/ST*1036E
10
AS/ST*1042E
10
AS/ST*1048E
10
AS/ST*1060E-2
10
ASF/STF1060E-3
15
ASR/STR2060E
15
AS/ST*1072E
15
ASR/STR2072E
15
ASR/STR2072E
20.0
*Applies to both ASF/STF front door models and ASR/STR rear door models.
TABLE 3
ELECTRIC HEATER DATA
208V 1Ø
Amp Draw
Circuit 1
Circuit 2
Circuit 1
36.1
-
30.8
36.1
-
30.8
36.1
-
30.8
36.1
-
30.8
16.0
32.0
41.7
16.0
32.0
41.7
16.0
32.0
41.7
16.0
32.0
41.7
24.0
48.1
41.7
24.0
48.1
41.7
24.0
48.1
41.7
24.0
48.1
41.7
48.1
48.1
41.7
MOTOR VOLTAGES/AMP DRAWS
Horsepower
3/4
Speed
Volts
120
Phase
Hertz**
50/60
Amps per Motor
7.5
** Operation at 50 HZ will generate approximately a 17% reduction in performance.
TABLE 2 - Motor Amp Ratings
FIGURE 6 - Removing Cover
VII. AIRFLOW ADJUSTMENTS
A. With the Air Door operating and the door in its full open position,
check to see that nothing is obstructing the air flow at the discharge
nozzle vanes.
B. Find the air stream split location. Hold a handkerchief, by its corners,
approximately 12" above the floor. Gently move the handkerchief
back and forth in the doorway. Make sure the air is being directed to
both the inside and the outside. The split location is indicated where
the handkerchief is vertical with minimal or no fluttering.
See Figure 7.
C. Adjust the discharge nozzle vanes so the split location is ap-
proximately 3" outside the doorway. This is accomplished by first
de-energizing the unit. Remove the cover housing, loosen the nozzle
vane locking screws and adjusting vanes.
D. Install remaining screws in cover housing.
240V 1Ø
240V 3Ø
Amp Draw
Amp Draw
Circuit 2
Circuit 1
-
20.8
-
20.8
-
20.8
-
20.8
-
27.8
-
27.8
-
27.8
-
27.8
20.8
41.6
20.8
41.6
20.8
41.6
20.8
41.6
41.7
27.8
4
3/4
3/4
1/2
1
1
1
3
208/240
480
120
1
1
1
1
50/60
50/60
50/60
3.8
1.8
7.2
240V 3Ø
Amp Draw
Circuit 2
Circuit 1
-
17.8
-
17.8
-
17.8
-
17.8
-
24.1
-
24.1
-
24.1
-
24.1
-
36.1
-
36.1
-
36.1
-
36.1
27.8
48.1
1/2
3
208/240
1
50/60
4.0
480V 3Ø
Amp Draw
Circuit 1
-
-
-
-
12.0
12.0
12.0
12.0
18.0
18.0
18.0
18.0
34.0