( F ) Fan Starter: Although not normally considered a
safety device, the fan starter is wired so that its 13-14
interlock powers the control system. Thus the main fan
must be energized before the gas system can be pow-
ered. This provides one more assurance, in addition to
the Airflow Switch, that the fan is operating before heat
comes on.
( G ) Secondary Safety** and Bleed Valves (or "Block &
Vent Va l v e s ) : A second main line gas valve is insta l l e d
downstream of the primary safety valve. A vent line with
an electrically operated normally-open valve takes off lat-
erally between the two main line valves. This vent line
must be piped to atmosphere outside the building, by the
customer on installation (See Suggestions for Regulator. )
I X .
O P E R ATION
G A S
SUPPLY
1000'S
P R E S S U R E
BTU/HR
( i n . w. g . )
5 "
700
6 "
765
7 "
820
8 "
G A S
SUPPLY
1000'S
P R E S S U R E
BTU/HR
( i n . w. g . )
5 "
790
6 "
865
7 "
930
8 "
990
* B a s e d o n 7 0 º F . i n l e t t e m p e r a t u r e .
( A ) Gas Adjustment: Heat output is adjusted by varying
t h e outlet pressure of the regulator (see Gas Pressure
Regulator). A pressure gage may be attached to the pip-
i n g a t a l e a k - t e s t c o n n e c t i o n . Table 1 shows performance
at various inlet pressures.
( B ) Pilot Adjustment: This heater is equipped with inter-
r u p t e d p i l o t ; i . e . , a f t e r m a i n b u r n e r i g n i t e s , p i l o t i s c u t o f f .
Scanner then senses main flame only. Pilot flame was
properly adjusted at the factory. F i e l d adjustment is pos-
sible by removing the protective cap and using a screw-
d r i v e r w i t h a s m a l l b i t .
MODEL B-22, 6500 CFM
RISE
FINAL T E M P.
( º F )
( º F ) *
99
109
117
7" MAX. RECOMMENDED
MODEL B-24, 7900 CFM
FINAL T E M P.
RISE
( º F ) *
( º F )
92
101
109
116
X .

MAINTENANCE

(Note: See wiring diagram for part number and manufacturer
of any control component. See manufacturer's instruction
sheets for more information.)
( A ) Fan Motor Bearings: Refer to green sheet on mainte-
nance of direct-connected fans. Most fan motors have a
1/8" NPT pipe at each bearing, which may be removed
for lubrication, in the event lube tubes were not factory-
i n s t a l l e d .
( B ) Burner: Side plates and their air holes should be
checked periodically, to be sure these pa r ts are not fouled
or plugged.
( C ) Burner Adjustment: (See Operation).
( D ) Fireye: The UVM-IF utilizes solid state components.
The only required maintenance is on its external compo-
nents; i.e., the Flame Rod and the Ultra -Violet Scanner.
See "Maintenance" in manufacturer's bulletin C-400.
( E ) Scanner: Remove scanner occasionally, c l e a n l e n s ,
and be sure that mounting pipe nipple is clear of insects
and d i r t .
169
( F ) Spark Ignitor: Ignition takes place by means of a spark
179
jumping from the ignitor to the side plate of the burner.
The spark gap should be 1/8" to 3/16" (. 12" -. 19"), and
187
located downstream of an air mixing hole, so that there is
a gas-air mixture to be ignited. Check for carbon "bridge"
between electrode and burner which may short out spark
and prevent ignition.
X I .
TROUBLESHOOTING
162
First check for loose wiring connections.
171
Then check the following for specific symptom:
179
( A ) Fan Won't Start -
186
( 1 ) Selector in "OFF" position.
( 2 ) Check 3-phase line leads for power across all 3
phases, if one line is dead, check fuses or breaker in
main disconnect.
( 3 ) Check fuse on control circuit transformer.
( 4 ) Try "SUM" setting. If fan runs, but won't run on "@",
check 1T'HS outdoor thermostat (if used) for open R-B
contact; check limit switch on door for open-contact.