6.
CAPACITY TABLE
6-1.
COOLING CAPACITY
This table is created using the maximum capacity.
MODEL
: ABG18LV
AFR
13.0
°CDB
18
°CWB
12
°CDB
TC
SHC
-10
4.35
3.28
0
4.26
3.24
5
4.14
3.18
10
4.00
3.12
15
4.04
3.14
20
5.16
3.63
25
4.94
3.54
30
4.71
3.45
35
4.66
3.43
40
3.53
2.90
46
2.50
2.46
AFR : Air Flow Rate (m
3
/min)
TC : Total Capacity (kW)
SHC : Sensible Heat Capacity (kW)
IP : Input Power(kW)
21
23
15
16
IP
TC
SHC
IP
TC
SHC
0.39
4.84
3.30
0.40
5.01
3.59
0.46
4.74
3.26
0.46
4.90
3.54
0.57
4.61
3.20
0.58
4.77
3.48
0.68
4.45
3.14
0.69
4.61
3.41
0.59
4.50
3.16
0.60
4.65
3.43
1.28
5.75
3.65
1.30
5.95
3.97
1.43
5.51
3.57
1.46
5.70
3.88
1.59
5.25
3.47
1.61
5.43
3.78
1.88
5.19
3.45
1.91
5.37
3.75
1.34
3.93
2.92
1.36
4.06
3.18
1.01
2.79
2.47
1.02
2.88
2.69
Indoor temperature
25
27
18
19
IP
TC
SHC
IP
TC
SHC
0.40
5.34
3.60
0.40
5.50
3.89
0.47
5.23
3.56
0.47
5.39
3.84
0.58
5.08
3.49
0.59
5.24
3.77
0.70
4.91
3.42
0.70
5.06
3.70
0.61
4.95
3.44
0.61
5.11
3.72
1.31
6.34
3.98
1.32
6.54
4.30
1.46
6.07
3.89
1.48
6.26
4.20
1.62
5.78
3.79
1.64
5.96
4.09
1.92
5.72
3.76
1.94
5.90
4.06
1.36
4.33
3.19
1.38
4.46
3.44
1.03
3.07
2.69
1.04
3.17
2.91
- (01 - 09) -
29
32
21
23
IP
TC
SHC
IP
TC
SHC
0.40
5.83
3.88
0.41
6.17
4.13
0.47
5.71
3.83
0.48
6.04
4.07
0.59
5.55
3.76
0.60
5.86
4.00
0.71
5.37
3.68
0.71
5.67
3.92
0.62
5.41
3.70
0.62
5.72
3.94
1.33
6.93
4.28
1.34
7.32
4.56
1.49
6.63
4.18
1.50
7.01
4.46
1.65
6.32
4.07
1.66
6.68
4.34
1.95
6.25
4.04
1.97
6.61
4.31
1.38
4.73
3.43
1.40
5.00
3.65
1.05
3.36
2.90
1.06
3.55
3.09
IP
0.41
0.48
0.60
0.72
0.63
1.35
1.52
1.68
1.99
1.41
1.07